Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 248 -
28 kW
Permitted
length
Pipe
Pipe total length (actual length)
≤ 250 m
L1+L2+L3+L4+L5+L6
+L7 + a+b+..i
Actual length
≤ 150 m
Farthest pipe length(m)
Equivalent length
≤ 175 m
L1+L3+L4+L5+L6+i
Pipe
length
Equivalent length L of pipe from the first
branch to the farthest one (m)
≤ 40 m
L3+L4+L5+L6+i
Outdoor unit up
≤ 50 m
——
Drop height between
indoor unit and outdoor
unit
Outdoor unit down
≤ 30 m
——
Drop
height
Drop height between indoor unit and indoor
unit
≤15m ——
Conversion of the equivalent length: Convert into the direct pipe length. According to branch
Junction 0.5m/l and branch header pipe 1.0m/l.