Controller
___________________________________________________________________________________
- 305 -
1) Common Display Data
Common display data will be indicated in all display pages.
a. Figure
means CCM is in network control with PC or Gateway.
b. Figure
means CCM is in communication connection with Function Module.
c. Figure
means CCM is in communication connection with Message Remote Control
Module.
d. Figure
means CCM is in communication connection with Telephone Remote Control
Module.
e. If CCM is in normal communication with NIM, then (Blank),
●
,
will be displayed in
dynamic circulation. Otherwise, no any display.
f. Lock
Symbol
means the CCM is in Lock state or the buttons are in Lock state. ON means
the buttons are in Lock state or both CCM and Buttons are in Lock state, and 0.5 second flash
means the CCM is in Lock state.
g. When setting page layout, if the selected air-conditioner is in Remote Controller Lock state
(in case that several air-conditioners are in operation, if only one is in Remote Controller Lock
state, then that means in Lock state.), symbol
will display steadily. If in Mode Lock state,
symbol
will flash in 0.5Hz. If Remote Controller Lock state and
Mode Lock state exist at the same time, symbol
will display steadily.
2) Display Data Treatment
Data Display area adopts 7-segment code, and there are 5 groups of 2-digital 7-segment
display.
a. TEMP. Display
TEMP. Display is applicable to the following: Set Temp. Ts
(
17-30
℃)
, Indoor Return Air
Temp. T1, Evaporator Pipe Temp. T2A, Evaporator Middle Pipe Temp. T2B, Condenser Pipe
Temp. T3. And the allowable data display range is 0
℃
--99
℃
. If higher than 99
℃
, then display
99
℃
. If lower than 0
℃
, then display 0
℃
. What’s more, the real display range also has
relationship with the PCB temperature checking range. If no effective data, then display “-“and
Unit symbol
℃
will be ON.
b. CURRENT Display
CURRENT display is applicable to Compressor Current. The allowable range is 0A-99A. If
no effective data, then display “-“and Unit symbol mp will be ON.
Summary of Contents for R-410A
Page 103: ...Wall mount 102 Part 4 2 Wall Mounted...
Page 113: ...Wall mount 112 4 Dimensions 4 1 YDS 22 36EC 4 2 YDS 45 56EC...
Page 115: ...Wall mount 114 5 Piping Diagrams 5 1 YDS 22 56EC 5 2 YDS 22 56HC...
Page 116: ...Wall mount 115 6 Wiring diagrams 6 1 YDS 22 36EC 6 2 YDS 45 56EC...
Page 117: ...Wall mount 116 6 3 YDS 22 56HC...
Page 118: ...Wall mount 117 7 Sound level 7 1 Test condition 7 2 Noise spectrums YDS 22 36EC HC...
Page 119: ...Wall mount 118 YDS 45 56EC HC...
Page 120: ...Wall mount 119 8 Velocity temperature distribution Discharge angle 70...