Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 247 -
4. Installation of Refrigerant Pipe
4.1) The permitted length and drop difference of refrigerant pipe.
10-14 kW
Digital scroll
Pipe
Pipe total length (actual length)
≤100m
L1+L2+L3+L4+L5+L6+A+
B+C+D+E
10 kW
≤45m
Actual length
14 kW
≤60m
10 kW
≤55m
Farthest pipe
length(m)
Equivalent length
14 kW
≤70m
L1+L3+L4+L5+L6+E
Pipe
length
Equivalent length L of pipe from the first
branch to the farthest one (m)
≤20m L3+L4+L5+L6+E
Outdoor unit up
≤20m
——
Drop height
between indoor unit
and outdoor unit
Outdoor unit
down
≤20m ——
Drop
height
Drop height between indoor unit and
indoor unit
≤8m ——