Diagnostic Status Detail
Bit
Diagnostic Status Detail
Description
Diagnostic
status
assignment
bit
NAMUR
Diagnostic Status Detail.1
Bit31
AMP ERR
Amplifier failure
Bit27
F
Bit30
MEMORY ERR
Memory failure
Bit27
F
Bit27
Firm Update ERR
Firmware write error
Bit27
F
Bit26
ADC ERR
ADC failure
Bit27
F
Bit23
SENSOR1 FAILURE
Sensor 1 burnout
Bit26
F
Bit22
SENSOR2 FAILURE
Sensor 2 burnout
Bit26
F
Bit21
TERM SNS FAILURE
CJC sensor burnout
Bit26
F
Bit16
CRITICAL LOWBAT
Detection of an extreme decrease in the
battery voltage
Bit20
M
Bit15
LOWBAT
Detection of a decrease in the battery voltage
Bit19
M
Bit11
FIRMWARE CONDITION CHECK
Internal control error detection
Bit21
M
Diagnostic Status Detail.2
Bit31
SENSOR1 TEMP HI
Sensor 1 temperature higher limit scale out
Bit22
O
Bit30
SENSOR1 TEMP LO
Sensor 1 temperature lower limit scale out
Bit22
O
Bit29
SENSOR2 TEMP HI
Sensor 2 temperature higher limit scale out
Bit22
O
Bit28
SENSOR2 TEMP LO
Sensor 2 temperature lower limit scale out
Bit22
O
Bit27
AMB TEMP HI
Ambient temperature higher limit scale out
Bit22
O
Bit26
AMB TEMP LO
Ambient temperature lower limit scale out
Bit22
O
Bit23
SENSOR1 SPAN ADJ ERR
Sensor 1 faulty input of span adjustment
value
Bit25
C
Bit22
SENSOR1 ZERO ADJ ERR
Sensor 1 faulty input of zero adjustment value Bit25
C
Bit21
SENSOR2 SPAN ADJ ERR
Sensor 2 faulty input of span adjustment
value
Bit25
C
Bit20
SENSOR2 ZERO ADJ ERR
Sensor 2 faulty input of zero adjustment value Bit25
C
Bit15
AI1 O/S MODE
AI1 O/S Mode
Bit24
C
Bit14
AI2 O/S MODE
AI2 O/S Mode
Bit24
C
Bit13
AI1 SIMULATE MODE
AI1 Simulate Mode
Bit17
C
Bit12
AI2 SIMULATE MODE
AI2 Simulate Mode
Bit17
C
F0901.ai
AI algorithm
Filtering
PV
AI publish
Simulate
value
Sensor
Signal
SIMULATE
Linearization
INPUT_RANGE
SENSOR_CONNECTION
Linearization
SCALE
PV_FTIME
Data Publication Period
Scale
Transducer
value
EXT_RJ_VAL
RJ.
RJ_TEMP RJ_TYPE
BIAS
LIN_TYPE
Switch
Input
MODE.Target
NO REF
+
+
PV_TYPE
PV
PV
PV
MODE and
PV.Status handling
O/S
Auto
Man
Operator
Operator
Operator
Figure 9.1
Example schema of analog input object