<9. Parameter Summary>
9-6
IM 01C50E01-01EN
Object
ID
Attribute
ID
Label
Description
Default value Handling
5.
AI1 block
6.
AI2 block
(continued)
103
Cal Point Lo
Sets the zero-point adjustment for the input adjustment (zero-
gain adjustment ) of the sensor.
Be sure to perform adjustment with Cal Point Lo (zero-point)
first.
---
W
104
Cal Point Hi
Sets the gain-point adjustment for the input adjustment (zero-
gain adjustment) of the sensor.
---
W
105
Cal Point Clear
Resets the input adjustment value of the sensor to the factory
setting.
0
W
106
Process Value
Type
Selects data to output to PV.Value.
0. % value after the scaling process is performed
1. Actual target value after the filter process is performed
0
W
107
Reference
Junction Unit
Sets the unit for Reference Junction Temp and External
Reference Junction Value.
Select any of °C (Celsius), K (Kelvin), °F (Fahrenheit), and °R
(Rankine).
°C
W
108
Burn Out Type
Sets the burnout of the PV value at the detection.
0: The direction specified by hard ware switch
1: Set to higher side
2: Set to lower side
0
W
(Note) R: Read only, W: Read and Write
(Note) “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specification) according to NAMUR NE107.
*1:
NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”