<7. Setting Parameters>
7-8
IM 01C50E01-01EN
7.3.5 Setup the Integral Indicator
As for the integral indicator display, either the
temperature, voltage, resistance or the % value
of the temperature, voltage, resistance can be
selected and displayed. The display is in the output
format of the process value.
Specify AI block to display on the LCD.
■ LCD display parameter (Display Selection)
Select AI block to display on the LCD from AI1
or AI2.
■ Call up the display parameter (Process Value
Type)
AI1 block: Configuration: Process Value Type
Either actual target value (Direct) or % (Indirect)
can be selected.
7.3.6 Power Saving Mode Setting
Enabling the power saving mode on prolongs
the battery life of the transmitter, in which the
transmitter's measurement and calcutattion are
suitable for general use with a gradual change
in the process and ambient temperature. On the
other hand, when the power saving mode is set to
off, the transmitter is capable of a steep change in
the process and ambient temperature wtih its high
responsiveness trading off of the battery life.
■ Procedure to call up the power saving mode
TRANSDUCER block : Power Saving Mode
Off: Disable
On: Enable
7.3.7 Unit
The unit for the process value is set at the factory.
The specified unit of the input sensors set (°C if not
specified).
When the unit of the temperature, voltage, and
resistance is displayed, set the Process Value Type
parameter to actual target value (Direct).
And sensor type set by the sensor type setting
parameter (Lin Type) must be corresponded with
the unit displayed.
When using the resistance temperature sensor or
the thermocouple sensor, unit displayed set °C or
others, using voltage, set mV, and using resistance,
set ohm.
The unit can be set by following the procedure
below.
■ Procedure to call up the unit parameter (Units
Index)
AI1/AI2 block: Scale : Units Index
To change the unit, select the desired unit from
the displayed unit list.
7.3.8 Measurement Range
The unit parameter is set at the factory before
shipment if specified at the time of order. To change
the measurement range, follow the procedure
below.
■ Procedure to call up the lower limit setting
parameter (EU at 0%)
AI1/AI2 block : Scale : EU at 0%
■ Procedure to call up the upper limit setting
parameter (EU at 100%)
AI1/AI2 block: Scale : EU at 100%
Set the lower limit setting parameter (EU at 0%)
and upper limit setting parameter (EU at 100%)
to the unit specified in the unit parameter (Units
Index).