<2. Notes on Handling>
2-5
IM 01C50E01-01EN
1
2
3
4
5
Temperature
Transmitter
Battery
pack
Hazardous Location
Antenna
(*1)
Arrester
(*1, *2)
Temperature Sensor (*1)
(One or Two sensors)
*1: These apparatus are simple apparatus.
*2: Arrester may not be connected.
Antenna Connector
F0204.ai
[Installation Diagram]
Note 4. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void FM
Approvals approval.
Note 5. Battery Pack
USE ONLY BATTERY PACK YOKOGAWA
F9915MA OR F9915NS.
Note 6. Special Conditions for safe use
POTENTIAL ELECTROSTATIC CHARGING
HAZARD-SECURE DISTANCE OF 100MM
FROM ANTENNA.
DO NOT OPEN WHEN CL II, III, DIV 1,2
ATMOSPHERE IS PRESENT.
2.7.2 CSA Certification
Caution for CSA intrinsically safe type. (Following
contents refer “DOC. No. ICS031)
Note 1. Model YTA Series temperature transmitters
with optional code /CS17 are applicable for
use in hazardous locations.
Certificate: 2328785
• Applicable standard: CAN/CSA-C22.2 No.0,
CAN/CSA-C22.2 No.0.4, C22.2 No.25,
CAN/CSA-C22.2 No.94,
CAN/CSA-C22.2 No.157, C22.2 No.213,
CAN/CSA-C22.2 No.61010-1,
CAN/CSA- C22.2 No.60079-0,
CAN/CSA-E60079-11, IEC60529
• Ex ia IIC T4
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D, Class II, Division 1,
Groups E, F & G, Class III, Division 1
• Nonincendive for Class I, Division2,
Groups A, B, C & D, Class II, Division2,
Groups F & G, Class III, Division1
• Enclosure: IP66/IP67 and Type 4X
• Temperature Code: T4
• Ambient Temperature: –50 to 70°C
Note 2. Output Parameters
• Sensor Circuit (Terminals: 1 to 5)
Uo = 6.6 V, Io = 66 mA,
Po = 109 mW, Co = 22 μF,
Lo = 8.1 mH
• The above parameters apply when one of
the two conditions below is given:
- the total Li of the external circuit (excluding
the cable) is < 1% of the Lo value or
- the total Ci of the external circuit (excluding
the cable) is < 1% of the Co value.
• The above parameters are reduced to 50%
when both of the two conditions below are
given:
- the total Li of the external circuit (excluding
the cable) is ≥ 1% of the Lo value and
- the total Ci of the external circuit (excluding
the cable) is ≥ 1% of the Co value.
• The reduced capacitance of the external
circuit (including cable) shall not be greater
than 1μF for Group IIB and 600nF for Group
IIC.
Note 3. Installation
• Installation should be in accordance with
Canadian Electrical Code Part I and Local
Electrical Code.
• The Hand Held Terminal must be CSA
certified.
• Do not alter drawing without authorization
from CSA.
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendive Certification.
1
2
3
4
5
Temperature
Transmitter
Battery
pack
Hazardous Location
Antenna
(*1)
Arrester
(*1, *2)
Temperature Sensor (*1)
(One or Two sensors)
*1: These apparatus are simple apparatus.
*2: Arrester may not be connected.
Antenna Connector
F0205.ai
[Installation Drawing]