<2. Notes on Handling>
2-7
IM 01C50E01-01EN
(3) Maintenance and repair
WARNING
The instrument modification or parts replacement
by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and
will void the certification.
(4) Name Plate
• Name Plate
: Refer to USER'S MANUAL.
Made in Japan
TOKYO 180-8750 JAPAN
MODEL
SUFFIX
SUPPLY
OUTPUT
MWP
mA DC
V DC
STYLE
CAL
RNG
NO.
F0207.ai
TEMPERATURE
TRANSMITTER
• Tag plate for intrinsically safe type
F0208.ai
POTENTIAL ELECTROSTATIC CHARGING HAZARD - SECURE DISTANCE
OF 100MM FROM ANTENNA.
USE ONLY BATTERY PACK YOKOGAWA F9915MA OR F9915NS.
POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.
WARNING
No. KEMA 10ATEX0163 X
Ex ia IIC T4 Ga
ENCLOSURE: IP66/IP67
Tamb.: -50 TO 70°C
Sensor input circuit (Terminal 1 to 5)
Uo=6.6V, Io=66mA, Po=109mW, Co=22
μ
F, Lo=8.1mH
*3
MODEL: Specified model code.
SUFFIX: Specified suffix code.
STYLE: Style code.
SUPPLY: Supply voltage.
OUTPUT: Output signal.
CAL RNG: Calibration range.
NO.: Serial number and year of production
*1
.
TOKYO 180-8750 JAPAN: The manufacturer
name and the address
*2
.
*1:
The first digit in the final three numbers of the serial
number appearing after “NO.” on the nameplate indicates
the year of production. The following is an example of a
serial number for a product that was produced in 2010:
91K819857 032
↑
The year 2010
*2:
“180-8750” is a zip code which represents the following
address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3:
The identification number of Notified Body.
2.7.4 IECEx Certification
Caution for IECEx Intrinsically safe type.
Note 1. Model YTA Series temperature transmitters
with optional code /SS27 for potentially
explosive atmospheres:
• No. IECEx KEM 10.0073X
• Applicable Standard:
IEC 60079-0: 2011, IEC 60079-11: 2011,
IEC 60079-26: 2006
• Type of Protection and Marking code:
Ex ia IIC T4 Ga
• Ambient Temperature: –50°C to 70°C
• Enclosure: IP66/IP67
Note 2. Output Parameters
• Sensor input circuit (Terminals 1 to 5 )
Uo: 6.6 V
Io: 66 mA
Po: 109 mW
Co: 22 μF
Lo: 8.1 mH
• For the sensor input circuitry, these entity
parameters must be taken into account when
installed.
• The above parameters apply when one of
the two conditions below is given:
- the total Li of the external circuit (excluding
the cable) is < 1% of the Lo value or
- the total Ci of the external circuit (excluding
the cable) is < 1% of the Co value.
• The above parameters are reduced to 50%
when both of the two conditions below are
given:
- the total Li of the external circuit (excluding
the cable) is ≥ 1% of the Lo value and
- the total Ci of the external circuit (excluding
the cable) is ≥ 1% of the Co value.
• The reduced capacitance of the external
circuit (including cable) shall not be greater
than 1μF for Group IIB and 600nF for Group
IIC.
Note 3. Installation
• Installation should be in accordance with
local installation requirements.
(Refer to the Control Drawing)