<7. Setting Parameters>
7-2
IM 01C50E01-01EN
7.3 Setting Parameters
7.3.1 Parameter Usage and Selection
Before setting a parameter, please see the following
table for a summary of how and when each
parameter is used. This instrument is applicable for
not only single sensor input but also dual sensor
input assigned to AI1/AI2 accordingly.
IMPORTANT
After setting and sending data with the field
wireless configuration tool or the device
configuration tool, wait 30 seconds before
turning off the transmitter. If it is turned off
too soon, the settings will not be stored in the
transmitter.
Table 7.1
Parameter Usage and Selection
Item
Description
Tag No
Sets the tag No. for Device Tag (software tag). The tag No. can
be set Sixteen characters (alphanumeric characters, including
- and •).
Output mode
Allows outputting process value and self-diagnostic information
via field wireless network.
Either or all of temperature / voltage / resistance (AI1/AI2:
Process Value), and self-diagnostic information (UAPMO:
Diagnostic Status) can be set output data.
Range
Range corresponding for 0% to 100% signal is set with actual
input applied.
Integral indicator display setting
Sets the process value, bar graph to display on the LCD.
Display temperature unit setting
Sets the temperature unit to display.
Burnout setting
Sets the output status when the input sensor has burned out.
Zero-gain adjustment setting
Sets the input adjustment function using two adjustment
points..
Reset adjustment value
Reset the trim adjustment to the factory setting. The zero-gain
adjustment set by user can be returned to the factory setting.
Software write protect
Prohibit writing the setting data.
Adjustment information and memo field
Memo field available to write the check date, checker and
others (as an adjustment information ), or anything.
Operational mode
Set the operational mode of the sensor and integral indicator,
etc.
NOTE
Some of the parameter settings are in the
dialogue form called method, the on-line
instructions you can configure the parameters