<9. Parameter Summary>
9-2
IM 01C50E01-01EN
Object
ID
Attribute
ID
Label
Description
Default value Handling
1.
UAPMO
(continued)
106
EH Type
Available to write note into this parameter.
---
W
107
Power Supply
Voltage
Indicates the measured power supply voltage (V).
---
R
110
Hardware Write
Protect
Allows recognizing the status of the hardware write protection
switch.
0: Switch OFF
1: Switch ON
---
R
111
Radio Silence
Repeats a cycle of a 1-hour pause and 6-minute search if the
instrument cannot join the network after a time specified in
Radio Silence has elapsed. When 0 is set, the Radio Silence is
invalid.
28800
W
112
Simulation Active
Alert
The On/Off or priority for Simulation Active Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
113
Soft Update
incomplete Alert
The On/Off or priority for Soft Update incomplete Alert can be
set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
Not available for YTA.
1. TRUE
2. 15
W
114
Power low Alert
The On/Off or priority for Power low Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
115
Power Critical
low Alert
The On/Off or priority for Power Critical low Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
116
Fault prediction
Alert
The On/Off or priority for Fault prediction Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
Not available for YTA.
1. TRUE
2. 15
W
117
Environmental
conditions Alert
The On/Off or priority for Environmental conditions Alert can
be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
118
Outside sensor
limits Alert
The On/Off or priority for Outside sensor limits Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
119
Out of service
Alert
The On/Off or priority for Out of service Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
120
Callibration
problem Alert
The On/Off or priority for callibration problem Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
121
Faults Sensor or
actuator Alert
The On/Off or priority for Faults Sensor or actuator Alert can
be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
122
Faults
Electronics Alert
The On/Off or priority for Faults Electronics Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 1
1. TRUE
2. 15
W