5-21
IM XL100C-E
1
2
3
4
5
6
7
App
Index
Standard Protocol
Basic Setting Commands
• In order to activate the settings that are changed using the basic setting commands,
the basic settings must be saved using the XE command. Be sure to save the settings
with the XE command before starting the logging operation from a logging stopped
state. If you do not, the settings before the change are activated.
• The settings that are returned in response to a query while logging is stopped will
contain the new settings even if they are not saved with the XE command. However,
the new settings will not be activated until they are saved. In order to activate the new
settings, the XE command must be issued as described earlier. If you discard the
settings with the XE command or start the logging operation from a logging stopped
state before saving the settings with the XE command, the settings that are returned
in response to a query are those before the change.
Type
Command Function
Usable State
Administrator
User
Page
Setting
XA
Sets the alarm.
Logging stopped
Yes
No
5-32
XI
Sets the filter.
Logging stopped
Yes
No
5-32
XB
Burnout (query only)
All
Yes
Yes
5-33
XJ
RJC (query only)
All
Yes
Yes
5-33
XV
Sets the sampling interval.
Logging stopped
Yes
No
5-33
XS
Reserved
XM
Reserved
XT
Selects the temperature unit.
Logging stopped
Yes
No
5-33
XU
Sets the language.
Logging stopped
Yes
No
5-33
XR
Reserved
XQ
Reserved
RO
Reserved
RM
Reserved
XD
Sets the data save operation.
Logging stopped
Yes
No
5-33
XO
Selects the communication method.
Logging stopped
Yes
No
5-33
XZ
Selects the trigger.
Logging stopped
Yes
No
5-34
XK
Selects the start trigger.
Logging stopped
Yes
No
5-34
XL
Selects the end trigger.
Logging stopped
Yes
No
5-35
XH
Sets the key login and auto logout functions.
Logging stopped
Yes
No
5-35
XE
Sets whether or not to store the basic settings. Logging stopped
Yes
No
5-35
XG
Sets the time zone.
Logging stopped
Yes
No
5-36
XP
Reserved
XW
Sets the ID number.
Logging stopped
Yes
No
5-36
XY
Sets the statistical calculation.
Logging stopped
Yes
No
5-36
YA
Sets the IP address, subnet mask,
Logging stopped
Yes
No
5-36
default gateway, and DHCP function.
YD
Sets the Ethernet login function.
Logging stopped
Yes
Yes
5-36
YK
Sets the keepalive.
Logging stopped
Yes
No
5-36
YN
Sets the DNS.
Logging stopped
Yes
No
5-37
YE
Sets the SNTP (time synchronization function). Logging stopped
Yes
No
5-37
YQ
Sets the communication timeout.
Logging stopped
Yes
No
5-37
YS
Sets the serial interface.
Logging stopped
Yes
No
5-37
YO
Loads the setting data.
Yes
No
5-38
YI
Saves the setting data.
Logging stopped
Yes
No
5-38
YC
Resets the system (initializes the setup data).
Logging stopped
Yes
No
5-38
YT
Sets the FTP client.
Logging stopped
Yes
No
5-38
YG
Sets whether to use the Web server function.
Logging stopped
Yes
No
5-38
YL
Sets the operation of the Modbus master function. Logging stopped
Yes
No
5-39
YM
Sets the command of the Modbus master function. Logging stopped
Yes
No
5-39
Yes: Command usable
No: Command not usable
5.3 A List of Commands