5-27
IM XL100C-E
1
2
3
4
5
6
7
App
Index
Standard Protocol
p4
Span lower limit:
-99999
to
999999
p5
Span upper limit:
-99999
to
999999
p6
Span decimal place
x.xxxx:
0
xx.xxx:
1
xxx.xx:
2
xxxx.x:
3
xxxxx:
4
p7
Unit (up to 6 characters)
Set an arbitrary unit when the unit group is
set to ANY.
Enter a unit belonging to the unit group
when the unit group is not set to ANY (see
section 5.4, “Input Range Parameters”).
p8
Unit group
Sets the unit group (see section 5.4, “Input
Range Parameters”).
Query
SM[[ p1]?
Example
Set the communication channel number to
CO02, scaling value to 10.000, span lower limit
to -10.000, span upper limit to 15.000, and unit to
V.
SO CO02,ON,1.0000E02,-10000,15000,1,
V,VOLT.CURR.
Description • Only span parameters p4 and p5 can be
specified while logging is in progress.
• For parameters p4 and p5, enter a value using
5 digits or less, excluding the decimal, for
negative numbers and 5 digits or less for
positive numbers.
• For parameters p4, p5, and p6, either set all
three parameters or omit all three parameters
when logging is stopped.
• Set parameters p7 and p8 according to the
tables in section 5.4, “Input Range
Parameters” when p8 is not any.
SA
Sets the alarm
When not using the alarm
Syntax
SA p1,p2,p3<terminator>
p1
Channel number
Analog CH
8-CH input:
01
to
08
16-CH input:
01
to
16
Pulse CH
PL01
Logic CH
DI01
,
DI02
Calc. CH
CA01
to
CA32
Comm. CH
CO01
to
CO32
p2
Alarm number
1
(fixed)
p3
Alarm ON/OFF
OFF
Query
SA[ p1[,p2]]?
Example
Turn off the alarm of analog channel 10.
SA 10,1,OFF
Description This command cannot be issued while logging is
in progress.
When using the alarm
Syntax
SA p1,p2,p3,p4,p5,p6,p7,p8
<terminator>
p1
Channel number
Analog CH
8-CH input:
01
to
08
16-CH input:
01
to
16
Pulse CH
PL01
Logic CH
DI01
,
DI02
Calc. CH
CA01
to
CA32
Comm. CH
CO01
to
CO32
p2
Alarm number
1
(fixed)
p3
Alarm ON/OFF
ON
p4
Alarm type
High limit alarm:
H
Low limit alarm:
L
Window IN:
I
Window OUT:
O
Reserved
h
,
l
,
R
,
r
,
T
, and
t
(Characters are case-sensitive.)
p5
Alarm value1
p6
Relay setting
Relay ON:
ON
Relay OFF:
OFF
p7
Alarm output number
101
to
104
p8
Alarm value 2
Query
SA[ p1[,p2]]?
Example
Set a high limit alarm (alarm value 1 = 1000) to
channel 02, and activate relay number 1 when
an alarm occurs.
SA 02,1,ON,H,1000,ON,I01
Description • This command cannot be issued while logging
is in progress.
• When the input range setting (SR command)
is set to OFF, p3 cannot be turned ON.
• All alarm settings are turned OFF for the
following cases.
• When the input type is changed (VOLT,
TC, etc).
• When the input range is changed.
• When the span and scaling values are
changed during scaling display (includes
changing the decimal position).
• When the calculating equation is changed
or the span value is changed on a
calculation channel (CA01 to CA32).
• When the span and scaling values are
changed on a communication channel
(CO01 to CO32).
• For the range of alarm values of p5, see the
tables in section 5.4, “Input Range
Parameters.”
• Set the alarm value of a calculation channel
(CA01 to CA32) and communication channel
(CO01 to CO32) within the range of the span.
5.5 Setting Commands (Setting)