IM 12D08B02-01E
2-8 Specifications
Sensor
terminals 11-16
Max. cablelength: 60 mtr.
Cable dia. : 3…12 mm.
Sensor
terminals 11-16
Max. cablelength: 60 mtr.
Cable dia.: 3…12 mm.
Ùnclassified Location
FM Approved
Power Supply
(HART compatible)
Output
Supply
+
_
G
Classified Location
Unclassified Location
+
_
G
earth
earth
Intrinsically safe design
FM Class I, Div.1, Group ABCD,
T4 for ambient temp. < 55°C
T6 for ambient temp. < 40°C
SC202S transmitter
+
-
Load
Resistance
Classified Location
earth
+
_
24 volts DC Nominal
Supply Voltage.
FM Approved safety barrier or
power supply
with Rint = 300
:
(HART compatible)
For electrical data:
see text below.
For electrical data:
see text below.
Intrinsically safe design
FM Class I, Div.1, Group ABCD,
T4 for ambient temp. < 55°C
T6 for ambient temp. < 40°C
SC202S transmitter
Figure 1
Figure 2
Functional
Functional
Functional
・
Electrical data of the SC202S.
- Supply circuit (ter and ):
Maximum input voltage Vmax = 31.5 V. Maximum input current Imax = 100 mA.
Maximum input power Pmax = 1.2 W.
Effective internal capacitance Ci = 22 nF. Effective internal inductance Li = 35
P
H.
- Sensor input circuit (terminals 11 through 16) :
Maximum output voltage Vt = 14.4 V.
Maximum output current It = 10 mA.
Maximum allowed external capacitance
Ca = 59.36 nF.
Maximum allowed external inductance
La = 340 mH.
・
If Hand Held Terminal (HHT) is not connected to the power supply lines of the SC202S
(see figure 1):
Any FM Approved barrier or power supply may be used that meets the following requirements.
Voc or Vt
d
31.5 V ; Isc or It
d
100 mA; Ca
t
22nF + Ccable ; La
t
35
P
H + Lcable
If HHT is connected to the power supply lines of the SC202S (see figure 2):
The Hand Held Terminal must be FM Approved. Refer to the manufacturers control drawing of the
HHT and the barrier/power supply to determine the cable parameters.
(Voc or Vt ) + VHHT
d
31.5 V; (Isc or It ) + IHHT
d
100 mA;
Ca
t
22nF + CHHT ; La
t
35
P
H + LHHT
When installing this equipment, follow the manufacturer ’s installation drawing.
Installation should be in accordance with ANSI/ISA RP 12.06.01 “Installation of Intrinsically Safe
Systems for Hazardous (Classified) Locations” and the National Electrical Code (ANSI/NFPA 70).
Control equipment connected to the barrier/power supply must not use or generate more than 250
Vrms or Vdc.
・
Resistance between Intrinsically Safe Ground and earth ground must be less than 1.0 Ohm.
・
In case of using cable glands in Outdoor location, they shall be UV rated or made of metal.
WARNING
- Substitution of components may impair Intrinsic Safety
- To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or
read, understand and adhere to the manufacturer ’s’live maintenance procedures.
2-6. Control Drawing SC202S mA HART® Specification (FM Intrinsically safe design).
Application Doc. No.: IKE026-A10 P.5 to P.6
Summary of Contents for SC202G
Page 8: ...IM 12D08B02 01E LT LV PL EST SLO H BG RO M CZ SK...
Page 13: ...IM 12D08B02 01E 1 4 Introduction...
Page 33: ...IM 12D08B02 01E 2 20 Specifications...
Page 74: ...IM 12D08B02 01E Spare Parts 10 1 10 SPARE PARTS See Customer Maintenance Parts List...
Page 92: ...IM 12D08B02 01E 3 4 Appendix...
Page 96: ...IM 12D08B02 01E 3 8 Appendix...
Page 99: ...IM 12D08B02 01E Appendix 3 11 3 3 QIS 12D08B02 61E Figure 1 Testing Circuit and Test Equipment...
Page 100: ...IM 12D08B02 01E 3 12 Appendix...
Page 104: ...IM 12D08B02 01E 3 16 Appendix...