<6. CALORIE / PARAMETER SETTING>
6-15
IM 11T03E01-51E
2. Alarm-point Setting Mode [*ALARM
]
Set the upper /lower limits for the measured values of the parameters noted below, for the
purpose of raising an alarm.
(a) Select a parameter for which alarms are raised.
Physical density [*DENS]
Compensated density [*C_DNS]
Calorific value
[*CALRY]
Press the [YES] key to enter the desired mode when it is indicated.
(b) Set the upper/lower limits.
Physical density [*L_DNS], [*H_DNS]
Configure range:
00.0000 to 60.0000 (kg/m
3
),
0.00000
to
4.00000
(lb/ft
3
)
Compensated density [*L_CP.D], [*H_CP.D]
Configure range:
0.0000 to 6.0000 (kg/m
3
),
0.00000
to
0.40000
(lb/ft
3
)
Calorific Value
[*L_CAL], [*H_CAL]
Configure range:
000.000 to 133.000 (MJ/m
3
),
0.0000
to
3.5000
(kBTU/ft
3
)
*1:
See "Figure 6.4 Process at the Setting Level" on page 6-12.
*2: The display shows the previous parameter first.
[NO]
[ENT]
[ENT]
*ALARM
[ENT]
[NO]
XX.XXXX
*L_DNS
*CAL.DT
*SERVC
*DENS
XX.XXXX
*H_DNS
X.XXXX
*L_CP.D
X.XXXX
*H_CP.D
XXX.XXX
*L_CAL
XXX.XXX
*H_CAL
(Physical density)
(Compensated density)
(Calorific value)
*CALRY
[ENT]
[ENT]
[ENT]
[YES]
[YES]
[YES]
[NO]
[NO]
[NO]
*C_DNS
F0606.ai
[YES]
*
1
*
2
Figure 6.6
Process of the Alarm-point Setting Mode