<6. CALORIE / PARAMETER SETTING>
6-13
IM 11T03E01-51E
1. Analog Output Setting Mode [*RANGE
]
The analog output has output 1 and output 2. Only output 1 can be used for communication
purposes.
Set a range appropriate for 4-20 mA DC output signals. The range has two setpoints: the lower
limit (zero point) of the range corresponding to the minimum (0%) of a given output signal and the
upper limit (span point) of the range corresponding to the maximum (100%) of the given output
signal.
(1) Output 1 [*OUT1
]
(a) Select a parameter to be output.
Physical density [*DENS]
Compensated density [*C_DNS]
Calorific value
[*CALRY]
Gas temperature [*TEMP]
Gas pressure [*PRESS]
(b) Set the zero and span points. (This item is not applied if temperature or pressure are
chosen as the parameter in item (a) above.)
Physical density [*Z_DNS], [*S_DNS]
Configure range:
00.0000 to 60.0000 (kg/m
3
),
0.00000
to
4.00000
(lb/ft
3
)
Compensated density [*Z_CP.D], [*S_CP.D]
Configure range:
0.0000 to 6.0000 (kg/m
3
),
0.00000
to
0.40000
(lb/ft
3
)
Calorific value
[*Z_CAL], [*S_CAL]
Configure range:
000.000 to 133.000(MJ/m
3
),
0.0000
to
3.5000
(kBTU/ft
3
)
(2) Output 2 [*OUT2
]
The same parameters as those of item (1) apply.