4.4.4 Accessing parameter data
The following figure shows how the parameter data are mapped on the SDO objects:
Parameter data EtherCAT-Slot
Index
Module
Subindex
0x3102
SM 031 AI 2x 12Bit
01h, 02h
0x3103
FM 050 1x32Bit
01h ... 0Fh
For module parameterization SDO transfer takes place. Here the EtherCAT-Slot is
addressed via
index
. Via
subindexes
the corresponding parameters may be accessed.
The allocation of the subindexes may be found in the description of the corresponding
System SLIO module.
Parameter SLIO Module
Index:Sub
Name
Type
Offset
Access
Default
Description
0x3100...
0x313F:00
Parameter
U8
0
ro
Number of
parameters
Access to the parameters of the System SLIO
modules. Only modules with parameters are
mapped.
0x3100...
0x313F:01
Param1
U8
16
rw
Module parameter data
(see module description)
0x3100...
0x313F:02
Param2
U8
32
rw
0x3100...
0x313F: ...
...
Modules with no interrupt capability or whose diagnostic interrupt is de-
activated can not send an interrupt message on an error in parameteriza-
tion. Possible parameterization errors may be detected by means of a
diagnostic request after the parameterization.
Accessing the parameters
VIPA System SLIO
Deployment
Accessing the System SLIO > Accessing parameter data
HB300 | IM | 053-1EC01 | en | 18-49