Diagnostic Data (byte 1 ... n)
Index:Sub
Name
Type
Offset
Access
Default
Description
0x5005:00
Diagnostic Data
U8
0
ro
19
0x5005:01
Slot number
U8
16
rw
0
By reading this index here the EtherCAT-Slot of the
module may be found, to which the following diag-
nostic data belong to. By writing of an EtherCAT-Slot
to this index the diagnostic data of the corresponding
module may be read.
0x5005:02
Module error
U8
24
ro
0
Diagnostics data of the module (see module descrip-
tion)
0x5005:03
Module type
U8
32
ro
0
0x5005:04
Fix
U8
40
ro
0
0x5005:05
Communication/
Process interrupt
U8
48
ro
0
0x5005:06
Channel type
U8
56
ro
0
0x5005:07
Number of diag-
nostic bits
U8
64
ro
0
0x5005:08
Number of chan-
nels
U8
72
ro
0
0x5005:09
Channel error
U8
80
ro
0
0x5005:0A
Channel-specific
error channel 0
U8
88
ro
0
0x5005:0B
Channel-specific
error channel 1
U8
96
ro
0
0x5005:0C
Channel-specific
error channel 2
U8
104
ro
0
0x5005:0D
Channel-specific
error channel 3
U8
112
ro
0
0x5005:0E
Channel-specific
error channel 4
U8
120
ro
0
0x5005:0F
Channel-specific
error channel 5
U8
128
ro
0
0x5005:10
Channel-specific
error channel 6
U8
136
ro
0
0x5005:11
Channel-specific
error channel 7
U8
144
ro
0
0x5005:13
-
U8
152
ro
0
0x5005:14
µs-Ticker
U32
160
ro
0
Ä
‘Explanation of the elements’ page 71
The whole diagnostic data of a module may be accessed with this object. Here you may
either access current diagnostic data or the diagnostic data of a module on any
EtherCAT-Slot.
VIPA System SLIO
Deployment
Object Dictionary
HB300 | IM | 053-1EC01 | en | 18-49