9 Input Assemblies (Drive Produces)
66
YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
Error Code
Description
0x23
Writing Error during Undervoltage
Attempting to write during a drive Uv [Undervoltage] event.
0x24
Writing Error during Parameter Processing
Attempting to write while the drive is storing data.
Note:
Refer to the MEMOBUS/Modbus Data Table in the drive Technical Manual for a list of monitor data using the MEMOBUS/Modbus
message area.
◆
Standard Status 1 (Vendor Specific Yaskawa Electric (YE) Assy) - 151 (0x97)
Input Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
151
0
Fault
Alarm
Ready
Speed Agree
Reset
REV Running
ZSP
Running
1
-
-
1000-Series,
GA500: Multi-
Function
Photocoupler 2
GA700,
GA800, FP605:
Multi-Function
Digital Output 3
1000-Series,
GA500: Multi-
Function
Photocoupler 1
GA700,
GA800, FP605:
Multi-Function
Digital Output 2
1000-Series,
GA500: Multi-
Function
Digital Output
GA700,
GA800, FP605:
Multi-Function
Digital Output 1
LOCAL/
REMOTE
Uv
oPE
2
Output Frequency (Low Byte)
3
Output Frequency (High Byte)
4
Actual Torque (Low Byte)
5
Actual Torque (High Byte)
6
Actual Current (Low Byte)
7
Actual Current (High Byte)
Name
Description
Running
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Reset
Reset
0: -
1: Reset
Speed Agree
Speed Agree
0: -
1: Speed actual at speed reference
Ready
Drive Ready
0: Not Ready
1: Ready
Alarm
Drive Alarm
0: No Alarm
1: Alarm
Fault
Drive Fault
0: No Fault
1: During Fault
oPE
oPE
0: -
1: oPExx
Uv
Undervoltage
0: -
1: Undervoltage
LOCAL/REMOTE
Status of Run command from network
0: Run command is not from network
1: Run command is from network