9 Input Assemblies (Drive Produces)
62
YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
Name
Description
Reset
Reset
0: -
1: Reset
Speed Agree
Speed Agree
0: -
1: Speed actual at speed reference
Ready
Drive Ready
0: Not Ready
1: Ready
Alarm
Drive Alarm
0: No Alarm
1: Alarm
Fault
Drive Fault
0: No Fault
1: Fault
Service Code
Service Code
Refer to
for information.
Class
Class
Valid Classes are Control Supervisor Object (41) and AC/DC Object (42).
Instance will always be 1.
Attribute
Attribute
Data
Data
If Service Code is 0x94, Data is Error Code.
Output Frequency
Actual Drive Speed
Monitors drive output frequency.
Units are determined by parameter
o1-03 [Frequency Display Unit Selection]
.
Unit is not affected by Speed Scale SS.
Note:
This is a paired assembly (124/134).
Table 9.3 Reply Mapping - 134
Byte
Write Success
Read Success
Write Failure
Read Failure
Busy
Illegal Function
Code
Function Code
Equals Zero
1
0x90
0x8E
0x94
0x94
0x8E/0x90
0x94
0
2
Class Number
Class Number
0
0
Class Number
0
0
3
Attribute Number
Attribute Number
0
0
Attribute Number
0
0
4
0
Data Low Byte
DeviceNet Error
Code
DeviceNet Error
Code
0
0x08
0
5
0
Data High Byte
0xFF
0xFF
0
0xFF
0
Note:
For Error Codes, please refer to
Explicit Message Communications Errors on page 92
.
◆
Current Status Dynamic Assy (Vendor Specific Yaskawa Electric (YE) Assy) -
135 (0x87)
Input Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
135
0
Fault
Alarm
Ready
Speed Agree
Reset
REV Running
ZSP
Running
1
Service Code
2
Class
3
Attribute
4
Data (Low Byte)
5
Data (High Byte)
6
Actual Current (Low Byte)
7
Actual Current (High Byte)