18
YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
NOTICE
Damage to Equipment. When you touch the option, make sure that you observe correct electrostatic
discharge (ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry.
Note:
Remove the keypad, then move the keypad connector to the holder on the drive, then remove the front cover.
A - Holder
B - Keypad connector tab
C - Keypad connector
D - Drive front cover
E - Keypad
Figure 5.9 Remove the Front Cover and Keypad
3.
Carefully remove the LED Status Ring board (A) and put it in the temporary placement holes (B) on the
right side of the drive.
Refer to the drive manuals for more information.
NOTICE
Do not remove the LED Status Ring board cable connector. If you disconnect the LED Status Ring
board, it can cause incorrect operation and damage to the drive.
A - LED Status Ring board
B - Temporary placement holes
Figure 5.10 Remove the LED Status Ring Board
4.
Install the option (A) into the CN5-A connector (C) on the drive and use the included screws (B) to put it in
place.
Tighten the screw to a correct tightening torque:
• 0.5 N
∙
m to 0.6 N
∙
m (4.4 in
∙
lb to 5.3 in
∙
lb)
Note:
1. A ground wire is not necessary. Do not use the ground wire.
2. Only two screws are necessary to install the option on GA700 and GA800 drives.
3. The option package contains three screws and one ground wire.