9 Input Assemblies (Drive Produces)
YASKAWA
SIEP C730600 84G DeviceNet Technical Manual
53
Drive Type
Name
Terminal
Drive Model
Multi-Function Digital Output 3
P1-C1
CIPR-GA70Ax, CIPR-GA70Tx
M5-M6
CIPR-GA70Ux, CIPR-GA70Cx, CIPR-GA70Bx, CIPR-GA70Kx, CIPR-
GA70Dx
Multi-Function Digital Output 4
P2-C2
CIPR-GA70Ax, CIPR-GA70Tx
GA800
Multi-Function Digital Output 1
M1-M2
All
Multi-Function Digital Output 2
M3-M4
All
Multi-Function Digital Output 3
M5-M6
All
FP605
Multi-Function Digital Output 1
M1-M2
All
Multi-Function Digital Output 2
M3-M4
All
Multi-Function Digital Output 3
MD-ME-MF
All
*1
Terminals will change to M3-M4 depending on the model type of CIMR-xBx. Refer to the drive manuals for more information.
*2
Terminals will change to M5-M6 depending on the model type of CIMR-xBx. Refer to the drive manuals for more information.
9
Input Assemblies (Drive Produces)
The convention in this manual is from the PLC perspective. As such, an assembly is called an
“
Output Assembly
”
when outputted from the PLC and received by this node. An
“
Input Assembly
”
is outputted from this node and
read by the PLC. This section details
“
Input Assemblies
”
that are
“
Produced
”
by this drive.
◆
Basic Speed Control Input - 70 (0x46)
Input Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
70
0
-
-
-
-
-
Running 1
(FWD)
-
Fault
1
-
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Name
Description
Fault
Drive Fault
0: No Fault
1: Fault
Running 1 (FWD)
Forward Running
0: Stop or Reverse Running
1: Forward Running
Speed Actual
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency × 2
SS
(SS: Speed scale)
Range: 0 - 0xFFFF
For example, when output frequency of 4096 with a speed scale of 2
Speed actual data = 4096 × 2
2
= 16384 = 0x4000
Units are determined by parameter
o1-03 [Frequency Display Unit Selection]
.
Note:
Parameter
A1-02 [Control Method Selection]
determines whether the value for the speed monitor is the output frequency or the actual
motor speed.
Control Mode (A1-02)
Speed Actual
0
V/f
Output Frequency
0
H6-01 = 3 [Terminal RP Pulse Train Function = Speed
Feedback (V/F Control)]
V/f with Simple PG
Motor Speed
1
V/f with PG
Motor Speed
2
OLV
Motor Speed
3
CLV
Motor Speed
4
AOLV
Motor Speed
5
OLV for PM Motor
Output Frequency