4.4 MP2000 Series Machine Controller Parameter Details
4.4.3 Motion Monitoring Parameter Details
4-59
Motion Parameters
( 2 ) Over Range Parameter Number
IW
01
Parameter Number When Range Over is Generated
Range
Unit
0 to 65535
−
Description
Stores the number of a parameter set outside the setting range.
• Setting parameters: 0 or higher
• Fixed Parameters: 1000 or higher
This parameter stores the number of the setting or fixed parameter that exceeds the setting range either individually or in
combination with the settings of other parameters.
When motion fixed parameters are used, the parameter stores the parameter number plus 1000.