YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
335
H3-xx = B: PID Feedback
L5-04: Interval Method Restart Time
Y1-11: High Feedback Level
Y1-12: High Feedback Lvl Fault Dly Time
Y1-14: Feedback Hysteresis Level
HFB Fault: High Feedback Sensed
Figure 5.82 Auto Restart for High Feedback Detection when b5-09 = 1
■
L5-42: Feedback Loss Fault Retry Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-42
(3672)
Feedback Loss Fault Retry
Select
Sets the drive to try an Auto Restart when it drive detects an
FDBKL [WIRE Break]
fault.
0
(0, 1)
0 : No Retry
1 : Retry
■
L5-49: Fault Retry Speed Search Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-49
(3679)
Fault Retry Speed Search
Select
Sets the drive to do a speed search at the start of a Fault Retry.
1
(0, 1)
0 : Disabled
1 : Enabled
■
L5-50: Setpoint Not Met Fault Retry Sel
No.
(Hex.)
Name
Description
Default
(Range)
L5-50
(367A)
Setpoint Not Met Fault Retry
Sel
Sets the drive to try an Auto Restart when it detects an
NMS [SetPoint Not Met]
fault.
0
(0, 1)
0 : No Retry
1 : Retry
■
L5-51: Loss of Prime Fault Retry Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-51
(367B)
Loss of Prime Fault Retry
Select
Sets the drive to try an Auto Restart if it detects an
LOP [Loss Of Prime]
fault.
0
(0, 1)
0 : No Retry
1 : Retry
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...