278
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
H2-09: Modbus Register 2 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-09
(0B3C)
Modbus Register 2 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets
H2-09
with the address of the register that is output to
Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63]
and
uses the bit in
H2-10 [Modbus Register 2 Bit Select]
.
■
H2-10: Modbus Register 2 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to
Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63]
and uses the address
in
H2-09
.
■
H2-40: Mbus Reg 15E0h bit0 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-40
(0B58)
Mbus Reg 15E0h bit0
Output Func
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-41: Mbus Reg 15E0h bit1 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-41
(0B59)
Mbus Reg 15E0h bit1
Output Func
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-42: Mbus Reg 15E0h bit2 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-42
(0B5A)
Mbus Reg 15E0h bit2
Output Func
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-60: Term M1-M2 Secondary Function
No.
(Hex.)
Name
Description
Default
(Range)
H2-60
(1B46)
Expert
Term M1-M2 Secondary
Function
Sets the second function for terminal M1-M2. Outputs the logical calculation results of the terminals
assigned to functions by
H2-01 [Term M1-M2 Function Selection]
.
F
(0 - FF)
■
H2-61: Terminal M1-M2 Logical Operation
No.
(Hex.)
Name
Description
Default
(Range)
H2-61
(1B47)
Expert
Terminal M1-M2 Logical
Operation
Sets the logical operation for the functions set in
H2-01 [Term M1-M2 Function Selection]
and
H2-
60 [Term M1-M2 Secondary Function]
.
0
(0 - 8)
Note:
Refer to
Output of Logical Operation Results of MFDO on page 275
for more information about the relation between parameter settings and
logical operations.
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...