Table 5.59 Drive Operation in Normal Mode
b1-02 Settings
HOA Modes Transition
0 to 3
7 to 9
When you use the MFDIs set for
H1-xx = 6D and 6E [AUTO Command and HAND Command]
,
and
on
the HOA keypad do not function. When
S5-04 = 1
, use these MFDIs together.
Table 5.60 MFDI Settings and Drive Operation in Normal Mode
H1-xx = 6D
[AUTO Command]
H1-xx = 6E
[HAND Command]
Operation Mode
Frequency Reference Source
Run Command Source
OFF
OFF
OFF
Based on
b1-01
-
OFF
ON
HAND
Based on
S5-01
Keypad
ON
OFF
AUTO
Based on
b1-01
Based on
b1-02
ON
ON
OFF
Based on
b1-01
-