270
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
Refer to
“
PID control block diagram
”
for more information.
■
3E: PID Setpoint Selection 1
Setting Value
Function
Description
3E
PID Setpoint Selection 1
Sets the function to switch the PID setpoint to
YA-02 [Setpoint 2]
or
YA-04 [Setpoint 4]
. Set this function and
H1-xx = 3F [PID
Setpoint Selection 2]
at the same time.
Note:
If you use this function and one of
H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04]
at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-02
or
YA-04
is PID setpoint.
OFF : The frequency reference,
YA-01 [Setpoint 1]
, or
YA-03 [Setpoint 3]
is PID setpoint.
■
3F: PID Setpoint Selection 2
Setting Value
Function
Description
3F
PID Setpoint Selection 2
Sets the function to switch the PID setpoint to
YA-03 [Setpoint 3]
or
YA-04 [Setpoint 4]
. Set this function and
H1-xx = 3E [PID
Setpoint Selection 1]
at the same time.
Note:
If you use this function and one of
H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04]
at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-03
or
YA-04
is PID setpoint.
OFF : The frequency reference,
YA-01 [Setpoint 1]
, or
YA-02 [Setpoint 2]
is PID setpoint.
■
40: Forward RUN (2-Wire)
Setting Value
Function
Description
40
Forward RUN (2-Wire)
This function will not operate in a bypass system.
ON : Forward Run
OFF : Run Stop
■
44: Add Offset Frequency 1 (d7-01)
Setting Value
Function
Description
44
Add Offset Frequency 1 (d7-
01)
Sets the function to add the offset frequency set in
d7-01 [Offset Frequency 1]
to the frequency reference when the terminal
activates.
Note:
Refer to
d7: Offset Frequency on page 241
for more information.
■
45: Add Offset Frequency 2 (d7-02)
Setting Value
Function
Description
45
Add Offset Frequency 2 (d7-
02)
Sets the function to add the offset frequency set in
d7-02 [Offset Frequency 2]
to the frequency reference when the terminal
activates.
Note:
Refer to
d7: Offset Frequency on page 241
for more information.
■
46: Add Offset Frequency 3 (d7-03)
Setting Value
Function
Description
46
Add Offset Frequency 3 (d7-
03)
Sets the function to add the offset frequency set in
d7-03 [Offset Frequency 3]
to the frequency reference when the terminal
activates.
Note:
Refer to
d7: Offset Frequency on page 241
for more information.
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...