YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
421
■
YA-03: Setpoint 3
No.
(Hex.)
Name
Description
Default
(Range)
YA-03
(3E5A)
RUN
Setpoint 3
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
0.00
(0.00 - 600.00)
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-39 [PID User Unit Display Digits]
set the
unit, range, and resolution.
■
YA-04: Setpoint 4
No.
(Hex.)
Name
Description
Default
(Range)
YA-04
(3E5B)
RUN
Setpoint 4
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
0.00
(0.00 - 600.00)
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-39 [PID User Unit Display Digits]
set the
unit, range, and resolution.
◆
YC: Foldback Features
YC parameters
set Output Current Limit function.
■
Output Current Limit
The Output Current Limit function sets the current limit of motor. This function prevents long-term overload
conditions of motor when there is bearing degradation.
The drive will try to decrease the frequency reference to limit the output current. Parameter
YC-02 [Current Limit]
sets the current limit setpoint. When the motor current increases to more than the setpoint, the drive will decrease the
output frequency.
■
YC-01: Output Current Limit Select
No.
(Hex.)
Name
Description
Default
(Range)
YC-01
(3EBC)
Output Current Limit Select
Sets the function to enable or disable the output current regulator.
0
(0, 1)
0 : Disabled
1 : Enabled
■
YC-02: Current Limit
No.
(Hex.)
Name
Description
Default
(Range)
YC-02
(3EBD)
RUN
Current Limit
Sets the current limit.
0.0 A
(0.0 - 1000.0 A)
Note:
Value is internally limited to 300% of the drive rated current set in
n9-01 [Inverter Rated Current]
.
◆
YF: PI Auxiliary Control
PI Auxiliary Control lets the drive control pressure when the PI Auxiliary Level is adequate. When the PI Auxiliary
Control Level decreases to the PI Auxiliary Control Setpoint set in parameter
YF-03 [PI Aux Control Setpoint]
, the
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...