YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
319
Shows the motor protection operation time characteristics when overload occurs from continuous operation below
the motor rated current.
Figure 5.70 Protection Operation Time for a General-purpose Motor at Rated Output Frequency
■
L1-03: Motor Thermistor oH Alarm Select
No.
(Hex.)
Name
Description
Default
(Range)
L1-03
(0482)
Motor Thermistor oH Alarm
Select
Sets drive operation when the PTC input signal entered into the drive is at the
oH3 [Motor Overheat
Alarm]
detection level.
3
(0 - 3)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON and MB-
MC turns OFF.
1 : Coast to Stop
The output turns OFF and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows
oH3
, and operation continues. The output terminal set for
Alarm [H2-01 to H2-03 = 10]
turns ON.
■
L1-04: Motor Thermistor oH Fault Select
No.
(Hex.)
Name
Description
Default
(Range)
L1-04
(0483)
Motor Thermistor oH Fault
Select
Sets the drive operation when the PTC input signal to the drive is at the
oH4 [Motor Overheat Fault
(PTC Input)]
detection level.
1
(0 - 2)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON and MB-
MC turns OFF.
1 : Coast to Stop
The output turns OFF and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...