YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
677
No.
(Hex.)
Name
Description
MFAO Signal Level
U3-40
(301E)
Fault 7 MMDD
Shows the month and day when the seventh most recent fault occurred.
No signal output available
U3-41
(301F)
Fault 7 HHMM
Shows the time when the seventh most recent fault occurred.
No signal output available
U3-42
(3020)
Fault 8 YYYY
Shows the year when the eighth most recent fault occurred.
No signal output available
U3-43
(3021)
Fault 8 MMDD
Shows the month and day when the eighth most recent fault occurred.
No signal output available
U3-44
(3022)
Fault 8 HHMM
Shows the time when the eighth most recent fault occurred.
No signal output available
U3-45
(3023)
Fault 9 YYYY
Shows the year when the ninth most recent fault occurred.
No signal output available
U3-46
(3024)
Fault 9 MMDD
Shows the month and day when the ninth most recent fault occurred.
No signal output available
U3-47
(3025)
Fault 9 HHMM
Shows the time when the ninth most recent fault occurred.
No signal output available
U3-48
(3026)
Fault 10 YYYY
Shows the year when the tenth most recent fault occurred.
No signal output available
U3-49
(3027)
Fault 10 MMDD
Shows the month and day when the tenth most recent fault occurred.
No signal output available
U3-50
(3028)
Fault 10 HHMM
Shows the time when the tenth most recent fault occurred.
No signal output available
◆
U4: Maintenance Monitors
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-01
(004C)
Cumulative Ope Time
Shows the cumulative operation time of the drive.
Use parameter
o4-01 [Elapsed Operating Time Setting]
to reset this monitor. Use parameter
o4-02
[Elapsed Operating Time Selection]
to select the cumulative operation times from:
•
The time from when the drive is energized until it is de-energized.
•
The time at which the Run command is turned ON.
The maximum value that the monitor will show is
99999
. After this value is more than
99999
, the
drive automatically resets it and starts to count from
0
again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 0099H for
data in 1 h units.
10 V: 99999 h
U4-02
(0075)
Num of Run Commands
Shows how many times that the drive has received a Run command.
Use parameter
o4-13 [RUN Command Counter @ Initialize]
to reset this monitor. The maximum
value that the monitor will show is
65535
. After this value is more than
65535
, the drive
automatically resets it and starts to count from
0
again.
Unit: 1
10 V: 65535 times
U4-03
(0067)
Cooling Fan Ope Time
Shows the cumulative operation time of the cooling fans.
Use parameter
o4-03 [Fan Operation Time Setting]
to reset this monitor. The maximum value that
the monitor will show is
99999
. After this value is more than
99999
, the drive automatically resets it
and starts to count from
0
again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 009BH for
data in 1 h units.
10 V: 99999 h
U4-04
(007E)
Cool Fan Maintenance
Shows the cumulative operation time of the cooling fans as a percentage of the replacement life of
the cooling fans.
Use parameter
o4-03 [Fan Operation Time Setting]
to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is 90%.
10 V: 100%
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...