Counter...
2 7
Counter
...
–
For parametrization of the digital I/O periphery and the technological
functions the corresponding sub modules of the CPU 314C-2 PN/DP
(314-6EH04-0AB0 V3.3) is to be used.
–
The controlling of the operating modes of the technological functions
happens by means of handling blocks of the user program.
Since the CPU from VIPA is configured as Siemens CPU, so the setting of the non- VIPA
specific parameters takes place via the Siemens CPU. For parametrization click in the
Project area
respectively in the
Device overview
at the CPU part. Then the parameters of
the CPU part are shown in the
Properties dialog
. Here you can make your parameter set-
Chapter 4.7 ‘Setting standard CPU parameters’ on page 66
1.
Switch in the
Project area
to
‘Network view’
.
2.
After installing the GSDML the IO device for the SLIO CPU may be found in the
hardware catalog at
Other field devices > PROFINET > IO > VIPA GmbH > VIPA
SLIO System
. Connect the slave system to the CPU by dragging&dropping it from
the hardware catalog to the
Network view
and connecting it via PROFINET to the
CPU.
3.
Click in the
Network view
at the PROFINET part of the Siemens CPU and enter at
valid IP address data in
‘Properties’
at
‘Ethernet address’
in the area
‘IP protocol’
.
4.
Enter at
‘PROFINET’
a
‘PROFINET device name’
. The device name must be
unique at the Ethernet subnet.
Setting standard CPU
parameters
Connection SLIO CPU as
PROFINET IO device
VIPA System SLIO
Configuration with TIA Portal
TIA Portal - Hardware configuration - CPU
HB300 | CPU | 013-CCF0R00 | en | 16-40
221