5.7.3 Proceeding
In the Siemens SIMATIC Manager the following steps should be executed:
1.
Perform a hardware configuration for the CPU.
Chapter 4.4 ‘Hardware configura-
2.
Double-click the counter sub module of the CPU 314C-2 PN/DP.
ð
The dialog
‘Properties’
is opened.
3.
As soon as you select the operating mode for the corresponding channel, a dialog
box with default values for this counter mode is created and shown. Select for the
corresponding channel the operating mode
‘Frequency counting’
.
‘Counter operating modes’ on page 115
4.
Perform the required parameter settings.
5.
Safe your project with
‘Station
è
Safe and compile’
.
6.
Transfer your project to your CPU.
n
The
Chapter 5.7.4 ‘SFB 48 - FREQUENC - Frequency measurement’ on page 131
should cyclically be called (e.g. OB 1) for controlling the frequency measurement.
n
The SFB is to be called with the corresponding instance DB. Here the parameters of
the SFB are stored.
5.7.4 SFB 48 - FREQUENC - Frequency measurement
The SFB 48 is a specially developed block for compact CPUs for frequence measure-
ment.
n
The SFB FREQUENC should cyclically be called (e.g. OB 1) for controlling the fre-
quency measurement.
n
The SFB is to be called with the corresponding instance DB. Here the parameters of
the SFB are stored.
n
Among others the SFB 48 contains a request interface. Hereby you get read and
write access to the registers of the frequency meter.
n
So that a new job may be executed, the previous job must have be finished with
JOB_DONE
= TRUE.
n
Per channel you may call the SFB in each case with the same instance DB, since the
data necessary for the internal operational are stored here. Writing accesses to out-
puts of the instance DB is not permissible.
n
With the SFB FREQUENC (SFB 48) you have following functional options:
–
Start/Stop the frequency meter via software gate SW_GATE
–
Read the status bit
–
Read the evaluated frequency
–
Request to read/write internal registers of the frequency meter.
Name
Declaration
Data type
Address
(Inst.-DB)
Default value
Comment
LADDR
INPUT
WORD
0.0
300h
This parameter is not evaluated.
Always the internal I/O periphery
is addressed.
CHANNEL
INPUT
INT
2.0
0
Channel number
SW_GATE
INPUT
BOOL
4.0
FALSE
Enables the Software gate
Hardware configuration
User program
Description
Parameters
VIPA System SLIO
Deployment I/O periphery
Frequency measurement > SFB 48 - FREQUENC - Frequency measurement