When disabled, the PROFIBUS interface operates as a server for communication serv-
ices with the following characteristics:
n
The PROFIBUS interface gets an "passive" PROFIBUS node, this means it is not
involved in the token rotation.
n
Via this interface you have PG/OP functions (programming, status request, control,
test).
n
The speed of the PG/OP functions is limited.
n
Bus rotation time is not influenced.
n
S7 routing is not possible.
8.2 Fast introduction
The PROFIBUS DP slave is to be configured in the hardware configurator from Siemens.
Here the configuration happens by the sub module X1 (MPI/DP) of the Siemens CPU.
To switch the interface X3 MPI(PtP) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
ment storage media - VSD, VSC’ on page 83
For the configuration of the PROFIBUS DP master please follow the following approach:
n
Enable bus functionality via VSC
n
Hardware configuration - CPU
n
Deployment as DP master or DP slave
–
With activating the bus function
‘PROFIBUS DP master’
by means of the VSC,
the bus function
‘PROFIBUS DP slave’
is also unlocked.
n
Transfer of the complete project to CPU
With the Siemens SIMATIC Manager, the CPU 013-CCF0R00 from VIPA
is to be configured as
CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3)
The integrated PROFIBUS DP master (X3) is to be configured and con-
nected via the sub module X1 (MPI/DP).
8.3 Hardware configuration - CPU
The configuration of the CPU takes place at the Siemens
‘hardware configurator’
. The
hardware configurator is part of the Siemens SIMATIC Manager. It serves for project engi-
neering. Please use for configuration the Siemens SIMATIC Manager V 5.5 SP2 and up.
The modules, which may be configured here are listed in the hardware catalog. If neces-
sary you have to update the hardware catalog with
‘Options
è
Update Catalog’
.
For project engineering a thorough knowledge of the Siemens SIMATIC
Manager and the Siemens hardware configurator is required!
Overview
Steps of configuration
Precondition
VIPA System SLIO
Option: PROFIBUS communication
Hardware configuration - CPU
HB300 | CPU | 013-CCF0R00 | en | 16-40