5.5.3 Parametrization
5.5.3.1
Address assignment
Sub module
Output address
Access
Assignment
DI24/DO16
136
BYTE
Digital output Q+0.0 ... Q+0.7 (X5)
137
BYTE
Digital output Q+1.0 ... Q+1.3 (X5)
5.5.4 Status indication
Digital output
LED
green
Description
DO +0.0 ... DO +0.7
●
Digital output Q+0.0 ... 0.7 has "1" signal
○
Digital output Q+0.0 ... 0.7 has "0" signal
DO +1.0 ... DO +1.3
●
Digital output Q+1.0 ... 1.3 has "1" signal
○
Digital output Q+1.0 ... 1.3 has "0" signal
Power supply
LED
green
Description
1L+
●
DC 24V electronic section supply
○
DC 24V electronic section supply not available
2L+
●
DC 24V power section supply outputs OK
○
DC 24V power section supply outputs OK
3L+
●
DC 24V power section supply SLIO bus OK
○
DC 24V power section supply SLIO bus not available
5L+
●
DC 24V power section supply inputs OK
○
DC 24V power section supply inputs not available
Error
LED
red
Description
1F
●
Error power supply sensor
○
no error
2F
●
Error at overload respectively short circuit at the outputs
○
no error
on: ● | off: ○
VIPA System SLIO
Deployment I/O periphery
Digital output > Status indication
HB300 | CPU | 013-CCF0R00 | en | 16-40
100