5.
Pull the module group forward.
6.
For mounting turn all the locking lever of the module group to be mounted upwards.
7.
To mount the module group put it to the gap between the both modules and push it,
guided by the stripes at both sides, to the mounting rail.
8.
Turn all the locking lever downward, again.
9.
Plug again the electronic module, which you have removed before.
10.
Wire your module group.
ð
Now you can bring your system back into operation.
2.7 Trouble shooting - LEDs
Each module has the LEDs RUN and MF on its front side. Errors or incorrect modules
may be located by means of these LEDs.
In the following illustrations flashing LEDs are marked by ☼.
Behaviour
: After PowerON the RUN LED of each module is off and the MF LED of each
module is sporadically on.
Reason
: The maximum current for the electronic power supply is exceeded.
Remedy
: As soon as the sum current of the electronic power supply is exceeded, always
place the power module 007-1AB10.
Behaviour
: After PowerON the MF LED of one module respectively more modules
flashes. The RUN LED remains off.
General
Sum current of the elec-
tronic power supply
exceeded
Error in configuration
VIPA System SLIO
Basics and mounting
Trouble shooting - LEDs
HB300 | CPU | 013-CCF0R00 | en | 16-40