14
Function
Prompt
C
2
2
Communica-
tions address
C
2
3
Communica-
tions condi-
tions
C
2
4
Cold junction
compensation
C
2
5
Selection of
time-propor-
tional control
operation
0 to 127
0: 9600bps, 8bits, even parity, 1 stop bit
1: 9600bps, 8bits, no parity, 2 stop bit
2: 4800bps, 8bits, even parity, 1 stop bits
3: 4800bps, 8bits, no parity, 2 stop bits
0: Yes
1: No
0: Priority given to controllability
1: Priority given to life of control target (only
1 ON/OFF operation within the time-
proportional cycle)
0
0
0
0
Displayed on communications
model only
Communications disabled
when set to “0”
Displayed on communications
model only
Thermocouple input model
only
If a large fluctuation of the
manipulated variable occurs
during the time-proportional
cycle when this item is set to
“0”, control follows this
fluctuation. For this reason,
control may be turned ON and
OFF several times within the
cycle.
Factory
Setting
Function
Selections and Setting Range
Remarks
Display of Front Panel LED (SP1)
*See SP1 Lighting Pattern Table.
SP No. Display in
Operation Mode
Change of SP Value during
Selection (in Operation mode)
Chapter 5 INITIAL SETTINGS
C13 (number of SPs used and display method) Setting
1st digit: Number of SPs used
This digit sets the number of SP values that are used.
Setting
Number of SPs Used
0
1
1
2
2
3
3
4
2nd digit: Display/change method
Setting
0
OFF
Disabled
Pattern 1
1
ON
Disabled
Pattern 1
2
OFF
Enabled
Pattern 1
3
ON
Enabled
Pattern 1
4
OFF
Disabled
Pattern 2
5
ON
Disabled
Pattern 2
6
OFF
Enabled
Pattern 2
7
ON
Enabled
Pattern 2
• SP No. display in Operation mode
This setting selects whether or not to display the SP No. (SP0 to SP3) in the Operation mode.
• Change of SP value during selection
This setting selects whether or not to enable changing of the currently selected VP value.
• Display of front panel LED (SP1)
This setting is for distinguishing which SP value is currently selected by the lit/blinking state of
the front panel LED (SP1).
C
1 3
0 0 0 0
1st digit
2nd digit
3rd digit
4th digit