13
C
1
2
Operation
mode
C
1
3
Number of SPs
used and
display
method
C
1
4
Event 1
operation type
C
1
5
Event 2
operation type
C
1
6
Event opera-
tion in READY
mode
C
1
7
External switch
input 1 opera-
tion type
C
1
8
External switch
input 2 opera-
tion type
C
2
1
RDY
key
setting
Displayed on event
output model
Displayed on event
output model
Displayed on event
output model
Displayed on external
switch input model.
All operation types are
alternated.
Do not set the same
operation type No. to
external inputs 1 and 2.
(excluding 1: SP
switching)
When “1” (SP switch-
ing) is set for both C17
and C18, the four SP
values can be
switched.
RDY
key cannot be
operated when same
functions as external
switch input have been
set.
Function
Prompt
Function
Remarks
Factory
Setting
Selections and Setting Range
1st digit 0: Displays both SP and PV values
1: Displays SP value only
2: Displays PV value only
2nd digit 0: Does not display manipulated variable
1: Displays manipulated variable
3rd digit 0: Displays event settings or heater current value
1: Does not display event settings or heater current value
2: Does not display heater current only
4th digit 0: Displays time remaining of event timers/ Displays heater current and
event setting with a resolution of 1A
1: Does not display time remaining of event timers/ Displays heater current
and event setting with a resolution of 1A
2: Displays time remaining of event timers/ Displays heater current and
event setting with a resolution of 0.1A
3: Does not display time remaining of event timers/ Displays heater current
and event setting with a resolution of 0.1A
See page 14.
See page 15.
See page 15.
0: Operation continued in READY mode
1: Event output OFF in READY mode
0000
0000
0
0
0
0
Chapter 5 INITIAL SETTINGS
0000
0: Disabled
1: Switches between RUN and READY
2: Event latch canceled
3: Auto-tuning start/stop
4: SP value switching (two to four SP values)
Valid when the 1st digit of the number of SP
sets C13 is “1” or more.
Description
0: No operation
1: Switches between
No.0 SP and No.1
SP
2: Switches between
RUN and READY
3: Event 1 timer
operation
4: Event 2 timer
operation
5: Event 1 latch
canceled
6: Event 2 latch
canceled
7: Auto-tuning starts/
stops
Operation
when ON
No.1 SP
READY
Timer
activated
Timer
activated
Latch
canceled
Latch
canceled
Started
Operation
when OFF
No.0 SP
RUN
Timer reset
Timer reset
Latch
enabled
Latch
enabled
Stopped
C
1 2
0 0 0 0
1st digit
2nd digit
3rd digit
4th digit