28
Input type
Sampling cycle
PV bias
Set points
Setting indication range
Indication accuracy
Temperature unit switching
Model number
Output
Control action
Output rating
Differential gap
Output direct/reverse switching
Chapter 7
SPECIFICATIONS
Category
Item
Specifications
PV Inputs
Indicators
and Settings
Control
Outputs
Additional
Functions
Thermocouple:
K, J, E, T, R, DIN U, DIN L
RTD:
Pt100, JPt100
DC voltage:
1 to 5 V, 0 to 5 V, 0 to 1 V
500ms
-1999 to +9999 or -199.9 to +999.9
1 or 2 to 4
Input range display: See page 12 for details
±
0.5%FS
±
1 digit
Negative thermocouple area:
±
1%FS
±
1 digit
°
C/
°
F switchable
0D
Relay contacts
ON/OFF, time-proportional
Contact type: SPST
Contact rating: 250Vac, 3A,
30Vdc, 3A
Life: Min. 100,000 operations
(resistive load)
Min. switching specification:
5V, 100mA
6D
Voltage pulse (for SSR drive)
ON/OFF, time-proportional
Voltage (open):
22.5Vdc
±
15%
Internal resistance:
1100
Ω
±
5%
Leakage current (OFF):
100
µ
A max.
1 to 9999 or 0.1 to 999.9
Switchable
2 , SPST contacts, common shared
Contact rating: 250Vac 1A, 30Vdc 1A (resistive load)
PV upper limit alarm, PV lower limit alarm, PV upper/lower limit alarms,
deviation upper limit alarm, deviation lower limit alarm, deviation upper/
lower limit alarms, heater line break/overcurrent, control device short-
circuit, timer
Standby, latch, ON delay, controller alarm
0 to 9999 or 0.0 to 999.9
Min. 100,000 operations (resistive load)
5V, 10mA
1
AC 0 to 55A
AC 3 to 50A
±
3A
2
SP switching, RUN/READY switching, event latch state cancel, timer
event start/stop, auto-tuning start/stop
Dry contact or open-collector
• Allowable ON contact resistance:
Max. 250
Ω
• Allowable OFF contact resistance: Min. 100k
Ω
• Allowable ON residual voltage:
Max. 1.0V
• Terminal current voltage (open):
5Vdc
• Terminal current (ON):
Approx. 4mA
Event
Current
trans-
former
input
External
switch
input
No. of points
Type
Additional functions
Differential gap
Life
Min. switching
specifications
No. of points
Display range
Guaranteed
operating range
Accuracy
Recommended
operating conditions
No. of points
Function
Non-insulated type
No. Current
Thru Lines
Measuring
Current
CT Value
Display (ave.)
Allowable Input
Current
AC 3 to 15A
3
9 to 45A
Max. AC 33A
AC 5 to 23A
2
10 to 46A
Max. AC 50A
AC 9 to 50A
1
9 to 50A
Max. AC 100A