SAFETY REQUIREMENTS
To reduce risk of electrical shock which could cause personal injury, follow all safety notices
in this document.
This symbol warns the user of a potential shock hazard where hazardous live voltages may be
accessible.
* If the controller is used in a manner not specified by Yamatake Corporation, the protection provided
by the controller must be impaired.
* Do not replace any component (or part) not explicitly specified as replaceable by your supplier.
* All wiring must be in accordance with local norms and carried out by authorized and experienced
personnel.
* A switch in the main power supply is required near the equipment.
* Provide delayed type (T) fuses having a rated power supply of 200mA and voltage of 250V for the
mains power supply wiring of this AC power supply controller. (IEC 127)
EQUIPMENT RATINGS
Supply voltage
100 to 240Vac (operating power voltage 85 to 264Vac)
Frequency
50/60Hz
Power consumption
7VA max.
EQUIPMENT CONDITIONS
Do not operate the instrument in the presence of flammable liquids or vapors. Operation of any electrical
instrument in such an environment constitutes a safety hazard.
Temperature:
0 to 50
°
C
Humidity:
10 to 90%RH (condensation not allowed)
Vibration:
2m/s
2
(10 to 60Hz)
Over-voltage category: Category II (IEC60364-4-443, IEC60664-1)
Pollution degree:
2
EQUIPMENT INSTALLATION
The controller must be mounted into a panel to limit operator access to the rear terminals.
Make sure that the I/O common voltage and the grounding voltage excluding the power voltage are
33Vrms max., 46.7V (peak) max. and 70Vdc max.
APPLICABLE STANDARDS
EN61010-1, EN50081-2, EN50082-2, EN61326
The CE supported model is the C10T type (panel type) only.
H