12
Function
Prompt
C
0
1
Key lock
C
0
2
Temperature
unit
C
0
3
Control output
direction
C
0
4
Input type and
range
C
0
5
Decimal point
position
C
0
6
PV range
lower limit
C
0
7
PV range
upper limit
C
0
9
SP lower limit
C
1
0
SP upper limit
C
1
1
Manipulated
variable when
READY mode
or Alarm occur
0: Key lock not engaged
1: Key lock engaged for items other than SP
value, SP set selection, event value,
RDY
key
and AT
2: Key lock engaged for items other than SP
value, SP set selection and
RDY
key
3: Key lock engaged for all items
0:
°
C
1:
°
F
0: Reverse operation (heat control)
1: Direct operation (cooling control)
Thermocouple input range
1:
K
0 to
1200
°
C
0 to 2200
°
F
2:
K
0 to
600
°
C
0 to 1100
°
F
3:
K
0 to
400
°
C
0 to
700
°
F
4:
K -200 to
+400
°
C
-300 to +700
°
F
5:
J
0 to
800
°
C
0 to 1500
°
F
6:
J -200 to
+400
°
C
-300 to +700
°
F
7:
E
0 to
600
°
C
0 to 1100
°
F
8:
T -200 to
+400
°
C
-300 to +700
°
F
9: DIN U -200 to
+400
°
C
-300 to +700
°
F
10: DIN L
0 to
800
°
C
0 to 1500
°
F
11:
R
0 to
1600
°
C
0 to 3000
°
F
12:
S
0 to
1600
°
C
0 to 3000
°
F
RTD input range
21: Pt100 -200 to
+500
°
C
-300 to +700
°
F
22: Pt100
0 to
200
°
C
0 to
300
°
F
23: Pt100
0.0 to 200.0
°
C
0.0 to 300.0
°
F
24: JPt100 -200 to
+500
°
C
-300 to +700
°
F
25: JPt100
0 to
200
°
C
0 to
300
°
F
26: JPt100
0.0 to 200.0
°
C
0.0 to 300.0
°
F
27: Pt100
-50 to
+100
°
C
-50 to +150
°
F
28: Pt100 -50.0 to +100.0
°
C
-50.0 to+150.0
°
F
29: JPt100
-50 to
+100
°
C
-50 to +150
°
F
30: JPt100 -50.0 to +100.0
°
C
-50.0 to+150.0
°
F
DC voltage input range
42: 1 to 5Vdc
43: 0 to 5Vdc
44: 0 to 1Vdc
0: Decimal point not displayed (XXXX)
1: Decimal point No.1 display (XXX.X)
2: Decimal point No.2 display (XX.XX)
3: Decimal point No.3 display (X.XXX)
-1999 to +9999
-1999 to +9999
Setting range : PV range lower limit to SP upper
limit
Setting range : SP lower limit to PV range upper
limit
Setting range : 0 to 100% (no decimal point)
0
0
0
3
22
43
0
0
1000
Range
Min.
Range
Max.
0
Key lock can be
canceled anytime
Factory
Setting
Function
Selections and Setting Range
Remarks
Displayed on DC voltage
input models only
Displayed on DC voltage
input models only
Displayed on DC voltage
input models only
(Applied alarm code
A
L
0
1
,
0
2
,
0
3
,
7
0
,
9
8
)
Chapter 5 INITIAL SETTINGS
●
List of setup items