Operation mode
Operation mode
Parameter mode
PARA
PARA
PARA
Procedure
Power ON
This initial screen is displayed
for about 6 seconds.
The operation mode is
displayed.
Hold down the key for
3 seconds to advance to the
parameter mode.
The parameter mode is
displayed.
Use the , and
keys to enter numeric values.
To set other items, press the
key to display the item
and enter numeric values as
described in Step 4 above.
Hold down the key for 3
seconds twice or wait 1 minute.
Example: Change the control method
from "ON/OFF control" to "self-
tuning".
Current PV value
Current SP value
C
T
R
L
is displayed
0
is displayed
(default: ON/OFF operation)
Change to
1
(
1
: self-tuning)
The digit that is changed blinks for
about 2 seconds. Blinking stops
when the value is fixed.
Current PV value
(in the operation mode)
Current SP value
1
2
3
4
5
6
Chapter 5 INITIAL SETTINGS
1.Set “Latch Cancel” to the external switch input to turn the external switch ON.
2.Reset the additional event setting function (by setting the 3rd digit on C14 and C15 to “0”).
3.Turn the power OFF and back ON again.
4.Set “Latch Cancel” to the
RDY
key, and hold down the
RDY
key for at least one second.
Handling Precautions
Latch Cancel by the
RDY
key is enabled for both events 1 and 2. External switch input is
valid individually for events 1 and 2.
4
Controller alarm setting (C14 and C15 4th digit setting)
This function turns ON an event when a controller alarm code (AL01, AL02, AL03, AL70, AL97 and
AL98) is generated regardless of the direct/reverse setting of the operation mode. OR logic can be set on
the 1st digit of the event operation type.
Setting:
0: Disable
1: Enable
5-3
Parameter Settings
Control parameter settings are shown below.