VESDA-E VEP-A00-P Product Guide
www.xtralis.com
51
5.3
Security
The VEP-A00 has two levels of protection against unauthorized access. For connection via Ethernet, a
password of at least 8 characters must be used. After connection, a four digit PIN is used to control the
access level.
5.3.1
Ethernet Authentication
A password is used to authenticate access over Ethernet connection when using Xtralis VSC.
The password is set in the General options tab for the VEP-A00 detector, and applies to both Ethernet access.
Refer to Section 5.5.3 on page 56 and Section 1.0.1 on page 1 for further information. When creating
connection profiles in Xtralis VSC, the same password must be entered. Refer to Section 5.1.2 on page 45 for
further information.
The password must conform to the following rules:
l
8 or more characters.
l
Contains one or more numeric characters.
l
Contains both upper case and lower case characters.
5.3.2
Access Control
When accessing the VEP-A00 detector via Xtralis VSC, user functionality is initially limited. For additional
privileges, the user must log in to the detector using an 4 digit numeric PIN code. In Xtralis VSC, select Logon
from the Connection menu and enter the PIN.
User Level
Access Level
Functional Authorization
USR
Low
This is the USER or the OPERATOR level. The user can view
the event log and change the date and time. They can also
perform selected zone control functions.
ADM
High
At the ADMINISTRATOR level access is available to most
functions. These include setting alarm thresholds, normalizing
air flows, reset filter, and defining the relay configuration.
DST
Absolute
The DISTRIBUTOR level allows unlimited access to all the
system commands and parameters.
Table 5-1: User Access Levels
The default PIN for each level of user is set at the factory. The distributor has access to the PINs for each
level. PIN numbers are disclosed to authorized personnel attending accredited training courses.
After logging in the user has the option to change the default PIN. To guard against unauthorized access, if
someone enters an incorrect PIN number three times they will not be allowed another attempt for ten minutes.
Summary of Contents for VESDA-E VEP-A00
Page 2: ......
Page 8: ...VESDA E VEP A00 P Product Guide vi www xtralis com This page is intentionally left blank ...
Page 12: ...VESDA E VEP A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VEP A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 102: ...VESDA E VEP A00 P Product Guide 94 www xtralis com This page is intentionally left blank ...
Page 108: ...VESDA E VEP A00 P Product Guide 100 www xtralis com This page is intentionally left blank ...