VESDA-E VEP-A00-P Product Guide
www.xtralis.com
57
Static IP Address Configuration
l
IP Address:
IPV4 static address. This address must be used when creating a connection profile for the
detector in Xtralis VSC.
l
The default IP address is 192.168.0.200. This allows direct connection between a PC or Laptop and
the VEP-A00 using a standard Ethernet lead.
l
Prior to connecting the detector to a router or other gateway device, the default address must be
changed to an address in the range used by the router. This can be done by connecting to the
detector using the USB port.
l
Subnet Mask:
The subnet mask for the network.
l
Default Gateway:
The IP address of the router or other gateway device that is servicing the network.