VESDA-E VEP-A00-P Product Guide
82
www.xtralis.com
Installing the replacement Smoke Detector Chamber
1. Position the two indicated looms as shown in Figure 7-16. Position the indicated loom sections beside
the air flow sensing module, not on top of it. This will ensure that, when installing the chamber, the looms
are not caught between the chamber and the air flow sensing module.
Looms beside
module
Air flow sensing
module
Figure 7-16: Position the gray loom
2. Position the chamber looms (A) and (B) as shown in Figure 7-17.
A
B
Figure 7-17: Position the Chamber looms