975-0727-01-01
9
Freedom Inverter/Charger Configuration
Setting Battery Types on the Main Unit
You can attach different types of lead-acid batteries to the Freedom
HFS. Before installing batteries make sure that you configure the
unit to optimize the charging process.
The settings can be changed using display panel buttons. See “To
adjust the battery type setting:” on page 14.
Battery
Type
LED Screen
Bulk/
Absorption
Float
Flooded
(default)
14.4
13.5
GEL
14.2
13.8
AGM
14.3
13.4
Custom
changeable from 12.0 to 17.0
13.6 (default)
13.6 (default)
Viewing Inverter/Charger Information
The LED screen displays inverter/charger information as well as
feature settings in coordination with the LED lights underneath the
screen.
◆
Press the Select button to toggle between the following basic
information:
Info and Setting
LED Screen Info and Settings LED
Battery Voltage
.
(example)
Solid – Input Voltage (V)
Battery Current
(example) Solid – Input Current (A)
Inverter AC Output
Power
.
(example)
Solid – Output Power
(kW)
◆
Press and hold the Select button to view advanced setting
information. The display automatically exits after 5 seconds.
Info and Setting
LED Screen Info and Settings LED
Charging Current
Setting
or
or
or
none
Freedom HFS IC Owners Guide.book Page 9 Friday, September 11, 2015 2:54 PM
Summary of Contents for 807-1055
Page 2: ...Freedom HFS IC Owners Guide book Page ii Friday September 11 2015 2 54 PM ...
Page 12: ...Freedom HFS IC Owners Guide book Page x Friday September 11 2015 2 54 PM ...
Page 14: ...Freedom HFS IC Owners Guide book Page ii Friday September 11 2015 2 54 PM ...
Page 52: ...Freedom HFS IC Owners Guide book Page 38 Friday September 11 2015 2 54 PM ...
Page 56: ...Freedom HFS IC Owners Guide book Page 42 Friday September 11 2015 2 54 PM ...
Page 57: ...Freedom HFS IC Owners Guide book Page i Friday September 11 2015 2 54 PM ...