Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 121/165
Analog Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter
206
Configure
Analg.inp. YES
Configure analog inputs
YES/NO
Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES
.............. The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor
→
", "Digit
↑
" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO
................ The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Analog Inputs: Setting
•
Analog input 1
real power set point
•
Analog input 2
power factor set point
•
Analog input 3
0/4 to 20 mA
•
Analog inputs 4/5/6/7
Pt100
Fixed assignment of the inputs:
Analog
input 1 2 3 4 5 6 7
Type
0/4 to 20 mA
Pt100
Terminals 93/94/95
96/97/98
99/100/101 102/103/104
105/106/107 108/109/110 111/112/113
Function Real
power
set point
Power factor
set point
Alarm input