Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 129/165
Delayed Monitoring and Ignition Speed
Parameter
239
Monitoring on
after 00s
Delayed monitoring
0 to 99 s
Any parameters configured for delayed monitoring (e.g. oil pressure, generator un-
derfrequency, etc.) will not be assessed until the expiration of the time configured
here. This timer starts when the control unit detects that the engine has reached fir-
ing speed.
Parameter
240
Monitoring on
at f gen > 00Hz
Ignition speed
15 to 70 Hz
The user configures the point that the engine firing speed has been reached. Once
the controller detects this, the frequency controller assumes speed control.
Note
: Measurement is only possible above 15 Hz, even if 5 Hz are displayed.
Time [s]
Time [s]
Time [s]
Time [s]
Time [s]
Time [s]
G
ener
at
or
fr
equency
[H
z]
Nominal frequency
Delay
(configuration
screen B)
Delay
(configuration
screen B)
Configuration screen A
Case 2
'Release
Monitoring ON'
(Terminal 6/7)
Relay 4
'ON'
Case 1
'Release
Monitoring ON'
(Terminal 6)
Minimum
frequency
Minimum frequency für monitoring
(configuration screen A)
Configuration screen B
Monitoring ON
at f Gen > 00Hz
LED
'Monitoring ON'
(Watchdogs are active)
LED
'Monitoring ON'
(Watchdogs are active)
Monitoring ON
after 00s
Figure 6-6: Ignition speed - delayed monitoring