Battery Voltage Monitoring
Parameter
194
Batt.undervolt.
U < 00.0V
Battery voltage: limit
9.5 to 30.0 V
The battery undervoltage threshold value is configured in this screen. If the moni-
tored voltage reaches or is falls below this level for the configured delay time, the
unit issues an alarm.
Tripping of class F1 alarm
Parameter
195
Batt.undervolt.
Delay 00s
Battery voltage: delay
0 to 99 s
The battery undervoltage monitoring threshold limit must be exceeded, without in-
terruption, for the time period configured here before the configured relay will be
energized.
Note:
Regardless of the configured battery voltage watchdog, readiness for opera-
tion is withdrawn and a message is displayed if the power supply falls below
9 Vdc.