Operation Manual 37107F
MFR 3 - Multi Function Relay
Page 118/165
© Woodward
Discrete Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter
196
Configure
Dig.input YES
Configure discrete inputs
YES/NO
Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES
.............. The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor
→
", "Digit
↑
" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO
................ The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Blocking of Operation Mode Selector [D02]
Parameter
197
opMode blocking
via term.63 ON
Blocking of the operating mode selector
ON/OFF
ON
................ By enabling this discrete input [D02] (terminal 63), the operating
mode cannot be changed between MANUAL and AUTOMATIC by
pressing the push buttons.
OFF
.............. The discrete input is used as an alarm input.
Selection of the Mains Decoupling via Discrete Input [D01]
Parameter
198
Mains decoupling
via term.62 OFF
Mains decoupling via terminal 62
ON/OFF
ON
................ The designated mains decoupling breaker may be changed according
to the state of discrete input [D01]:
•
Discrete input [D01] (term. 62)
not energized
: decoupling via GCB
•
Discrete input [D01] (term. 62)
energized
: decouplingvia MCB
OFF
.............. The discrete input is used as an alarm input.