background image

Operation Manual 37107F 

MFR 3 - Multi Function Relay 

 

 

 

 

Page 104/165 

© Woodward 

Example: 
 
Initial conditions: 
Rated voltage V

n

 = 100 V 

Configured value I

p

 = 2.0*5 A = 10 A (rated current I

n

 = 5 A) 

 
Case 1 (monitored voltage V > 90% V

n

): 

As long as the monitored voltage exceeds 90% of the rated voltage, the configured value will not be adjusted. 
-> I

a

 = I

 
Case 2 (monitored voltage V < 90% V

n

 , but actual voltage V > knee curve setting): 

If the monitored voltage falls below 90% of the rated voltage, the configured value is adjusted proportionally 
with the ratio of monitored and rated voltage. 
-> I

a

 = (V/V

n

) * I

 
Case 3 (monitored voltage V < knee curve setting): 

If the monitored voltage falls below the percentage value of the rated voltage configured by the knee curve 
setting (Parameter 146), the configured value is adjusted to the proportional value at the knee curve setting. 
-> I

a

 = {(knee point setting in [%])/100} * I

If the knee curve setting is configured to 20% for example and the monitored voltage is lower than 20% of the 
rated voltage, the adjusted value I

a

 falls not below 20% of the configured value I

p

 
 

Parameter 

145

 

Inv.time ov.cur. 
V-restr.     ON  

Voltage restraint time-overcurrent 

ON/OFF 

ON

 ................ Inverse time-overcurrent monitoring with voltage restraint is enabled. 

The subsequent screens of this function are displayed. 

OFF

 .............. Inverse time-overcurrent monitoring is not performed. The subse-

quent screens of this function are not displayed. 

 

Parameter 

146

 

Inv.time ov.curr 
knee curve U>00% 

Voltage restraint time-overcurrent 

10 to 90 % 

The threshold limit for the voltage is defined in this parameter. The knee of the 
curve describes the lower limit of the threshold value lowering, i.e. the trip current 
belonging to this limit remains valid and will not be lowered further in case of an 
additional voltage drop. 

Tripping of alarm class 3 

 

Summary of Contents for MFR 3

Page 1: ...37107F Manual Software Version 3 4xxx Manual 37107F MFR 3 Multi Function Relay...

Page 2: ...urned off before disconnecting the battery from the system Electronic controls contain static sensitive parts Observe the following precautions to prevent dam age to these parts Discharge body static...

Page 3: ...ger corrected E 08 10 30 TE Minor corrections F 08 12 02 TE Minor corrections power display format Contents CHAPTER 1 GENERAL INFORMATION 9 Introduction 9 Measuring 11 Functional Range 12 CHAPTER 2 EL...

Page 4: ...7 LEDs 48 Push Buttons 49 General Configuration 49 Control of the Power Circuit Breakers 51 Operating Mode Selector 51 LC Display 52 Automatic Mode First Display Line Measuring Values 52 Automatic Mod...

Page 5: ...y Monitoring 111 Mains Voltage Monitoring 112 Mains d dt Phase Vector Shift Monitoring 114 Mains df dt Rate Of Change Of Frequency Monitoring ROCOF 116 Mains Decoupling Selection Between d dt and df d...

Page 6: ...1 CAN Bus Structure 152 CAN Bus 152 Current Direction Message 152 Power Set Point Value Message 153 CAN Bus Address Requirements 153 APPENDIX G LIST OF PARAMETERS 154 APPENDIX H SERVICE OPTIONS 160 Pr...

Page 7: ...rnal RC wiring for relay manager 27 Figure 3 20 Analog controller n f P wiring and jumper setting 27 Figure 3 21 Analog controller V Q wiring and jumper setting 27 Figure 3 22 Interface terminals 28 F...

Page 8: ...Table 4 3 Operating conditions dead bus start 32 Table 4 4 Operating conditions dead bus start conditions 32 Table 4 5 Operating conditions isolated operation 32 Table 4 6 Operating conditions mains...

Page 9: ...puts and real time clock Mounting B Flush mounting M DIN rail rear panel mounting Hardware variation non standard models e g custom relays Current transformer secondary 5 5 A Voltage transformer PT s...

Page 10: ...a unit fitted with all available options Inputs outputs functions configuration screens and other details described which do not exist on your unit may be ignored The present manual has been prepared...

Page 11: ...RMS current measurement Real power The control unit performs three phase true RMS power measurement This is accomplished by real time mul tiplication of the wye voltage and instantaneous conductor cu...

Page 12: ...face Standard Event recorder with real time clock Language manager for message texts Standard Ignition speed relay function Standard Running hours counter Standard Maintenance call counter Standard St...

Page 13: ...set point value for power factor Breaker logic open transition Standard Breaker logic closed transition Standard Breaker logic soft loading Standard Breaker logic parallel operation Standard Breaker...

Page 14: ...holders cigarette packages cellophane wrappers vinyl books or folders plastic bottles and plastic ash trays away from the control the modules and the work area as much as possible 4 Opening the contro...

Page 15: ...ed near to the device and in a position easily accessible to the opera tor This must also bear a sign identifying it as an isolating switch for the unit NOTE Connected inductive devices such as operat...

Page 16: ...alog input 4 T4 Pt100 Alarm input Command open GCB Generator current L1 Generator current L2 Generator current L3 Generator voltage L1 Generator voltage L2 Generator voltage L3 SPEED POWER Analog cont...

Page 17: ...1 Generator current L2 Generator current L3 Generator voltage L1 Generator voltage L2 Generator voltage L3 SPEED POWER three position controller or Analog controller output VOLTAGE POW FAC three posit...

Page 18: ...mm Note When used in a 12 Vdc system please wire the power supply as described above Measuring Inputs NOTE The three phase system must have a dextrorotatory field right handed rotary field If the uni...

Page 19: ...Busbar voltage L2 2 5 mm Mains L3 L2 L1 N Mains voltage MCB 52 L3 51 50 L2 L1 GCB G Figure 3 6 Measuring inputs voltage mains Terminal Measuring Description Amax 50 400 Vac direct or via measu ring t...

Page 20: ...e 3 7 Measuring inputs current generator Terminal Measuring Description Amax 25 Transformer 5 A Generator current L1 transformer term s2 l 2 5 mm 26 Generator current L1 transformer term s1 k 2 5 mm 2...

Page 21: ...B Reply Digital input D C 3 Figure 3 9 Discrete inputs control inputs Terminal Associated common Description according to DIN 40 719 part 3 5 8 3 Amax A B Make contact NO 3 7 Enable GCB 2 5 mm 5 Switc...

Page 22: ...4 Discrete input D03 alarm input or switch breaker logic 2 5 mm 65 Discrete input D04 alarm input 2 5 mm 66 Discrete input D05 alarm input 2 5 mm 67 Discrete input D06 alarm input 2 5 mm 68 Discrete i...

Page 23: ...PTC VDO 0 to 180 380 Ohm Analog input 0 to 5 V 0 to 10 V 0 to 150 mV Analog input 0 4 to 20 mA Analog input Pt100 or Pt1000 V Figure 3 12 Analog inputs Terminal Description according to DIN 40 719 par...

Page 24: ...ose GCB 2 5 mm 16 17 Command close MCB 2 5 mm 39 40 Command open MCB 2 5 mm 41 42 Command open GCB 2 5 mm Relay Manager A B Relay output external device max 250 Vac Figure 3 14 Relay outputs relay man...

Page 25: ...0 4 to 20 mA 1 5 mm Pulse Outputs B A Impuse output Open collector Figure 3 16 Pulse outputs Terminal Description Amax Real energy kWh A 137 Pulse output kWh pulse 1 5 mm B 136 Emitter Open Collector...

Page 26: ...oller 2 5 mm 12 raise 2 5 mm 13 lower 2 5 mm Multi Functional Controller Outputs The Option Q is a controller output for the following signals which can be selected in the configuration menu and by in...

Page 27: ...ontroller GND Speed power controller 8 10 9 GND PWM Speed Governor GND PWM PWM Speed power controller 8 10 9 A Voltage Speed Governor A U GND Speed power controller 8 A I 10 9 GND Current Speed Govern...

Page 28: ...L Y1 Y2 Y3 Y4 Y5 Figure 3 22 Interface terminals Wiring Description Whether the terminals are designated X or Y depends on the configuration of the system Please refer to the wiring diagram A X Y B X...

Page 29: ...esistance Note The termination must be effected with a resistor which corresponds to the wave impedance of the used cable e g 120 CAN bus CAN H CAN L GND Termination CAN bus CAN H Terminal resistance...

Page 30: ...ecified length for the communication bus wiring might not be achieved if wire of poor quality is utilized there is high contact resistance or other conditions exist Reducing the baud rate may overcome...

Page 31: ...ation point Input signals terminal Function Conditions Reply GCB is open 4 Enable GCB 3 Reply MCB is open 54 Enable MCB 53 1 0 x x Idle control A 1 0 x x N A B 1 1 x x Synchronization of the GCB C 0 x...

Page 32: ...ditions Isolated Operation Isolated operation Generator voltage and frequency are adjusted to the configured set point values by raising and lowering the controller outputs for voltage and speed frequ...

Page 33: ...rminal Function Conditions Isolated operation controller ON 35 Reply GCB is open 4 Enable GCB 3 Reply MCB is open 54 Enable MCB 53 x 0 x 0 x Mains parallel operation 0 OFF 1 ON x signal has no signifi...

Page 34: ...io of the real power to apparent power In a purely resistive circuit the voltage and current waveforms are instep resulting in a ratio or power factor of 1 00 often referred to as unity In an in ducti...

Page 35: ...ith the voltage the current is lagging leading The generator is over excited under excited Control If the control unit is equipped with a power factor controller a voltage lower signal is output as lo...

Page 36: ...via Enable MCB ON Additional information can be obtained from the descriptions of the configuration screens 1 3 2 4 Command close MCB 16 17 Time s Time s Time s Release MCB 53 7 Reply MCB is open 54 7...

Page 37: ...2 4 6 7 Command close GCB 14 15 Time s Time s Time s Time s Release GCB 3 7 Command open GCB 41 42 Reply GCB is open 4 7 Connection time GCB 5 Figure 4 3 Activation of the circuit breakers GCB ON OFF...

Page 38: ...n abrupt disturbance variable is applied to the control loop the reaction of the controlled system can be rec orded at the output as a function of time step response 0 t s x T T 1 0 T x x d m x d x m...

Page 39: ...al frequency monitor the amplitude and frequency If either of the two values change uncontrollably EMERGENCY SHUTDOWN Initial state The start position of the controller is determined using the initial...

Page 40: ...eturn the process to the tolerance band If the gain is con figured too high the result is excessive overshoot undershoot of the desired value Reset time Tn 00 0s Reset time Tn 0 2 to 60 0 s The reset...

Page 41: ...al power set point for the interchange A lower percentage influences the control more towards real power sharing The parameter kW kvar sharing reference variable kvar has no influence here Isolated op...

Page 42: ...not permissible 4 The recommended cable for use as the CAN bus cable is a Twisted shielded pair Ex Lappkabel Uni tronic LIYCY TP 2 2 0 25 UNITRONIC Bus LD 2 2 0 22 5 The CAN bus cable must not be rout...

Page 43: ...n the number of tool screen the numbers 1 to 8 with which you operate the MFR via LeoPC1 These numbers are identical to the unit numbers 7 Now start the LeoPC1 and load the corresponding configuration...

Page 44: ...rvolt 2 Generator time overcurrent level 1 99 F3 Gen overcurr 1 Generator time overcurrent level 2 99 F3 Gen overcurr 2 Reverse reduced load 96 F3 Revers min power Overload 97 F2 Gen overload Unbalanc...

Page 45: ...h button is pressed for 0 5 s t 2 5 s The terminal 36 is energized for 0 5 s t 2 5 s Result The Alarm LED changes from blinking to continually illuminated and the horn is silenced Acknowledgment via O...

Page 46: ...he left side The configuration plug is located on the left side of the unit The direct configuration cable DPC connects there MAN Stop MFR 3 V kV A L1 A L2 A L3 Mains Parallel ON V1 V2 V3 AUTO ACK Set...

Page 47: ...firm selection 13 Display V Route voltage display 13 Digit Increase digit 14 Set point Activate set point value 14 Cursor Move cursor one position right 15 Set point Increase MANUAL set point value 16...

Page 48: ...LED in the center of the 15 LED s indicates that the measured phase angle between the voltage systems displayed is less than 12 electrical The phase angle is only displayed if the frequencies of the t...

Page 49: ...Reply GCB is closed The GCB ON LED indicates that the GCB is closed when illuminated 11 MCB on Color Green Reply MCB is closed The MCB ON LED indicates that the MCB is closed when illuminated Push Bu...

Page 50: ...mode alterna tively the setpoint values for the operating modes AUTO MATIC or MANUAL can be changed Certain setpoint val ues which are entered into the unit from external sources can only be displaye...

Page 51: ...on mode has been enabled MCB ON Depending on which power circuit breaker logic has been se lected the MCB can be closed by pressing the MCB ON push button This process can be aborted if either the MCB...

Page 52: ...wer set point 2 or an external setpoint value is active The user may configure if set point 2 a 0 4 20 mA input or an interface is to be uti lized LC Display 28 LC display LC display The LC display sh...

Page 53: ...generator real power generator re active power determined using phase L1 current also if three phase power measurement was selected operating hours time remaining to the next maintenance call start c...

Page 54: ...dervolt Main overfrequency 111 F0 Mains underfreq Mains underfrequency 111 F0 Mains overfreq Mains phase vector jump 114 F0 Phase shift Mains df dt 116 F0 df dt error Battery undervoltage 117 F1 Batt...

Page 55: ...rates apply to each method Direct configuration 9 600 Baud 8 bit no parity 1 stop bit CAN bus configuration 125 kBaud CAUTION Please note that configuration only should be performed when system is not...

Page 56: ...ters and the setting limits are concerned The respective voltage values 1 or 4 are placed first to differentiate the two types Basic Data Language Manager Parameter 1 Sprache language Language first...

Page 57: ...mains and busbar voltage and frequencies the controller breaker and relay statuses during synchronization The specific displayed values are dependent upon the control unit hardware OFF The service dis...

Page 58: ...n the busbar and mains is displayed by the synchroscope LED strip M Mains voltage and frequency B Busbar voltage and frequency Status of Relays During Synchronization Rel MCB f V GCB Status of breaker...

Page 59: ...o hours after the last action is performed even if the configuration mode is accessed repeatedly If an incorrect password is entered the control unit reverts to code level CS0 and external users are b...

Page 60: ...rence The event recorder stores the last 50 alarms in a FIFO First In First Out format beginning with the most recent event By pressing the ACK push button the displayed alarm condition is deleted fro...

Page 61: ...etz Unterfreq Mains overfreq Mains vector phase jump Phasensprung Phase shift Mains df dt df dt Fehler df dt error Battery undervoltage Batt Unterspg Batt undervolt GCB synchronization time monitoring...

Page 62: ...owl Remote acknowledgment via terminal 36 Quittierung Kl 36 Acknowledg ter 36 Acknowledgment via push button ACK Quittierg Taste Ackn button QUIT Mains failure Netzausfall Mains failure Mains return N...

Page 63: ...If the following parameter direct para is configured to YES communication via the CAN bus ter minals X1 to X5 is disabled If communication is to be re established via the CAN bus after the unit is con...

Page 64: ...in this block are not displayed cannot be modified and are therefore skipped Parameter 12 Generator number 00 Generator number 1 to 4 For multiple generator applications that are coupled via a CAN bu...

Page 65: ...sf primary 00 000kV PTs primary generator 1 0 005 to 65 000 kV 4 0 020 to 65 000 kV The primary voltage is set here in kV This entry serves to indicate the primary vol tages in the display If a potent...

Page 66: ...rimary voltage is set here in kV This entry serves to indicate the primary vol tages in the display If a potential transformer is not used the measured voltage of 120V would be configured as 00 120kV...

Page 67: ...ump monitoring is not possi ble Parameter 24 Voltage meas Mains This screen affects the protective functions Voltage measurement system protection threephase singlephase The device can either monitor...

Page 68: ...A lower percentage may lead to malfunctions and additional inaccuracies in the control and monitoring functions also occur The primary rated current of the CT must be entered here It is indicated on t...

Page 69: ...A 00 0M W VA var S from 1000 kVA up to 10 MVA 000M W VA var S from 10 MVA 2 00 0k W VA var S up to 20 kVA 0000k W VA var S from 20 kVA up to 2000 kVA 00 0M W VA var S from 2000 kVA up to 20 MVA 000M W...

Page 70: ...ositive real power a positive real current flows in the k to l direction in the current transformer Positive re active power means that with a positive effective direction inductive re active lagging...

Page 71: ...T reaches the primary rated current the secondary rated current flows in the secondary winding of the CT Example for current transformer ratio 300 5 Current in the primary winding 300 A current in the...

Page 72: ...screen and entering it into the unit If power to the unit is cycled off the unit starts up in CS0 Parameter 32 Define level 1 code 0000 Assign code level 1 customer 0000 to 9999 This screen is only di...

Page 73: ...r is exported to the mains If insufficient power for the load requirements is generated remaining power required is imported from the mains Parameter 35 Power controller Pset1 I0000kW P controller set...

Page 74: ...ort power operation is enabled Frequency Controller Parameter 37 Initial state Frequency 000 f controller initial state 0 to 100 This value is the initial state or start value for the frequency contro...

Page 75: ...at in a steady state the actual value does not deviate from the generator frequency set point by more than the configured dead band value Synchronization The generator frequency is controlled in such...

Page 76: ...dc 5 Vdc 0 5V to 4 5V 0 5 to 4 5V 0 5 Vdc 4 5 Vdc 0 to 20mA 0 to 10V 0 to 10V 0 Vdc 10 Vdc 10 to 0mA 5 to 0V 5 to 0V 5 Vdc 0 Vdc 4 5V to 0 5V 4 5 to 0 5V 4 5 Vdc 0 5 Vdc 20 to 0mA 10 to 0V 10 to 0V 10...

Page 77: ...to prevent exces sive overshoot or undershoot Essentially this is the brakes for the process This portion of the PID loop operates anywhere within the range of the process unlike reset Voltage Control...

Page 78: ...ue Parameter 55 Volt controller time pulse 000ms V controller minimum ON period 20 to 250 ms The minimum ON period of the relay should be selected in such a manner that the voltage regulator responds...

Page 79: ...ponse is increased to permit larger corrections to the variable to be controlled The farther out of tolerance the process is the larger the response action is to return the process to the tolerance ba...

Page 80: ...oller refer to Voltage Controller on page 77 The settings for the voltage controller also affect the power factor controller External Power Factor Set Point Value Parameter 63 Power factor external ON...

Page 81: ...creased to permit larger corrections to the variable to be controlled The farther out of tolerance the process is the larger the response action is to return the process to the tolerance band If the g...

Page 82: ...oint value The more rapidly the change in the set point is to be carried out the greater this value must be Power Limitation Parameter 74 Power limit P max 000 P controller real power limitation maxim...

Page 83: ...to 20 mA or 4 to 20 mA analog input of the power factor controller is selected here depending on the type of input used 0 to 20 mA Minimum value of the setpoint is 0 mA maximum value is 20 mA 4 to 20...

Page 84: ...variable to be con trolled The farther out of tolerance the process is the larger the response action is to return the process to the tolerance band If the gain is configured too high the result is e...

Page 85: ...derivitive time constant If the re set time constant is too small the engine will continually oscilate If the reset time constant is too large the engine will take to long to settle at a steady state...

Page 86: ...er gene rators Mains parallel operation real power load sharing in reference to the oth er generators Parameter 90 Reactive power load share ON var sharing ON OFF ON Re active power is shared between...

Page 87: ...5 has been energized The generator can be given a remote start synchronized and the GCB can be opened via the CAN bus refer to Appendix F page 146 for a description of the interface telegram The gene...

Page 88: ...k may be accessed for modifica tions NO The parameters in this block are not displayed cannot be modified and are therefore skipped Breaker Logic Parameter 94 Breaker logic Breaker logic see below The...

Page 89: ...53 Enable MCB must be energized Breaker logic CLOSED TRANSITION make before break In this breaker logic the MCB and the GCB are synchronized in order to avoid a voltage free busbar Immediately after...

Page 90: ...to the busbar If a class F2 alarm occurs shutting the generator down is delayed by the time con figured here This gives another generator the opportunity to start and assume the load The generator is...

Page 91: ...systems to be connected cannot exceed the percentage value configured here for a connect command to be issued Parameter 102 Synchronize time pulse 0 00s Synch pulse time 0 02 to 0 26 s The duration o...

Page 92: ...ion is attempted until it is accomplished The subsequent screens of this function are not displayed Parameter 107 Sync time contr Delay 000s Synchronization time monitoring final value 10 to 999 s Whe...

Page 93: ...bus start max permissible differential frequency GCB 0 05 to 5 00 Hz The prerequisite to issuing a close command is that the monitored generator fre quency does not deviate from the generator rated f...

Page 94: ...se the Reply MCB is open is detected the relay manager func tion 92 relay is energized and an alarm message is displayed If the generator is load sharing the add on command is deleted so that another...

Page 95: ...externally CAUTION Mains power monitoring is not designed as a generator protective function If this function is to be used for generator protection it must be utilized in conjunction with an externa...

Page 96: ...d The subsequent screens of this function are displayed OFF Generator power monitoring is not enabled The subsequent screens of this function are not displayed Parameter 123 Rev red power resp value 0...

Page 97: ...ed or exceeded for the configured delay time the unit issues an alarm and opens the GCB Tripping of class F2 alarm without load shedding Parameter 127 Gen overload MOP Delay 00s Generator overload del...

Page 98: ...ured generator rated power If this level is reached or exceeded for the configured delay time the unit issues an alarm and opens the GCB Tripping of class F3 alarm Parameter 132 Reactive pow ind Delay...

Page 99: ...ercurrent monitoring Parameter 135 Gen overcurrent monitoring ON Time overcurrent monitoring ON OFF ON Generator overcurrent monitoring is enabled The subsequent screens of this function are displayed...

Page 100: ...Monitoring of overcurrents including inversely proportional time dependent tripping characteristic The selected trip curve defines the tripping time according to the measured current The tripping tim...

Page 101: ...00s Inverse time overcurrent time constant Tp 0 00 to 1 98s The time constant for tp is defined by this parameter Parameter 143 Inv time ov cur Ip 0 0 In Inverse time overcurrent current constant Ip 0...

Page 102: ...s tp 1 0 s tp 0 5 s tp 0 2 s tp 0 1 s tp 0 05 s tp 1 6 s I start Ip Figure 6 3 Inverse time overcurrent characteristic high inverse Extremely Inverse Ip In I start 1 1 x In 0 01 0 1 1 10 100 1000 1 1...

Page 103: ...excitation cannot be maintained As a result the unit cannot maintain power in order to initiate a voltage independent overcurrent delay The voltage restraint functionality reduces the overcurrent thre...

Page 104: ...portional value at the knee curve setting Ia knee point setting in 100 Ip If the knee curve setting is configured to 20 for example and the monitored voltage is lower than 20 of the rated voltage the...

Page 105: ...toring is enabled The subsequent screens of this function are displayed OFF Ground fault monitoring is not performed The subsequent screens of this function are not displayed Parameter 148 Earth fault...

Page 106: ...oring ON Unbalanced load ON OFF ON Generator load imbalance monitoring is enabled The subsequent screens of this function are displayed OFF Generator load imbalance monitoring is not performed The sub...

Page 107: ...g is not performed The subse quent screens of this function are not displayed Parameter 154 Gen overfreq 1 f 00 00Hz Generator overfrequency limit 1 40 00 to 85 00 Hz The value for overfrequency limit...

Page 108: ...r underfrequency monitoring is not performed The subse quent screens of this function are not displayed Parameter 159 Gen underfreq 1 f 00 00Hz Generator underfrequency limit 1 40 00 to 85 00 Hz The v...

Page 109: ...If the monitored vol tage reaches or exceeds this level for the configured delay time the unit issues an alarm and opens the GCB This value refers to the secondary voltage of the genera tor PT inputs...

Page 110: ...is configured in this screen If the monitored voltage reaches or falls below this level for the configured delay time the unit is sues an alarm and opens the GCB This value refers to the secondary vol...

Page 111: ...function are not displayed Parameter 174 Mains overfreq f 00 00Hz Mains overfrequency limit 40 00 to 70 00 Hz The value for the mains overfrequency limit is configured in this screen If the mo nitore...

Page 112: ...Mains voltage monitoring refers to the phase phase voltages VPh Ph U Ph N Mains voltage monitoring refers to the phase neutral voltages VPh N Parameter 180 Mains overvolt U Ph Ph 000V Mains overvoltag...

Page 113: ...F0 alarm Parameter 184 Mains undervolt U Ph N 000V Mains undervoltage limit 1 20 to 87 V 4 20 to 300 V The phase neutral voltage value for mains undervoltage limit is configured in this screen If the...

Page 114: ...n the permissible range The voltage vector exceeds the configured limit value for the phase vector shift The breaker configured for mains decoupling is opened The requirement therefore is a mains para...

Page 115: ...e phase d dt phase vector shift limit single phase 3 to 30 Tripping occurs if the electrical angle of the voltage curve shifts in any one phase by more than this configured angle If the value is reach...

Page 116: ...OFF Mains frequency monitoring is not performed The subsequent screens of this function are not displayed Parameter 191 df dt monitoring release 0 0Hz s df dt ROCOF limit 1 0 to 9 9 Hz s The value to...

Page 117: ...is level for the configured delay time the unit issues an alarm Tripping of class F1 alarm Parameter 195 Batt undervolt Delay 00s Battery voltage delay 0 to 99 s The battery undervoltage monitoring th...

Page 118: ...ers in this parameter block may be accessed for modifica tions NO The parameters in this block are not displayed cannot be modified and are therefore skipped Blocking of Operation Mode Selector D02 Pa...

Page 119: ...ond breaker logic may be configured during the configuration of the dis crete inputs When discrete input D03 is energized the second breaker logic is enabled Discrete inputs Setting Discrete input 1 2...

Page 120: ...d alarm class to each discrete alarm input The monitoring functions are divided into four alarm classes F0 Warning alarm This alarm does not lead to an interruption of the operation An alarm message i...

Page 121: ...utton or modifications can be made to the parameters Cursor Digit or Select push buttons This does not disable or enable individual parameters only if the individ ual parameters in this parameter bloc...

Page 122: ...are dis played with an exclamation mark Parameter 209 Limit warning 000 C Analog input Pt100 warning limit 1 0 to 255 C The limit value at which a warning occurs is configured here Tripping of class F...

Page 123: ...r 215 Analog input x 0 00mA x 1 7 Analog input 0 4 to 20 mA measuring range 0 to 20 mA 4 to 20mA The input range 0 to 20 mA or 4 to 20 mA is selected in this screen If 4 to 20 mA is selected here and...

Page 124: ...ire break has been assessed by the control the threshold limit monitoring for the analog input is deactivated Measuring range monitoring tripping at 4 to 20 mA 2 mA negative deviation Pt100 240 C posi...

Page 125: ...ich may be confi gured is located in Appendix D Each parameter is assigned a unique number The parameter may be scaled via an upper and a lower input value The analog outputs may also be assigned an e...

Page 126: ...ction NOT operator logical function 1 2 3 Function numbers the following applies before Example of logical conditions and relevant texts Requested function Programming Relay energizes if function 22 i...

Page 127: ...Pulse per positive kWh 0 1 to 150 0 The number of pulses per measured unit to be output is configured here Ex If 20 kWh have been measured and Pulse kWh 020 00 has been configured a total of 20 kWh 20...

Page 128: ...d and can either be viewed Select push button or modifications can be made to the parameters Cursor Digit or Select push buttons This does not disable or enable individual parameters only if the indiv...

Page 129: ...int that the engine firing speed has been reached Once the controller detects this the frequency controller assumes speed control Note Measurement is only possible above 15 Hz even if 5 Hz are display...

Page 130: ...B NOTE Please note chapter Breaker Logic starting page 88 for description of the breaker logics Parameter 241 Download and open GCB ON Shutdown ON OFF ON The GCB is opened following power reduction if...

Page 131: ...alarm message will be displayed when the counter expires Refer to Parameter 244 for a de scription of the maintenance call function OFF The maintenance call counter is disabled Parameter 244 Service...

Page 132: ...operation This permits the user to display the correct number of engine hours if this controller is used on an older engine or this controller is to replace an older controller NOTE If the control uni...

Page 133: ...IC mode 2 Navigate to the display screen Start counter 00000 using the Select button 3 Press and hold the Digit push button for 7 seconds kWh kvarh Counter Parameter 249 Display kWh on YY Display kWh...

Page 134: ...ekday 00 0 Day and weekday user defined The day and weekday of the internal clock are configured Day 01 1st day of the month 02 2nd day of the month 31 31st day of the month if available Weekday 1 Mon...

Page 135: ...other signals may lead to malfunctions and damage the unit the engine and or components connected to the unit CAUTION Please consider that the unit does not have an internal rotating field monitoring...

Page 136: ...ng mains parallel operation change the operating mode from AUTOMATIC to MANUAL Open the MCB MCB ON LED will turn off Press the AUTOMATIC pushbutton to return the control unit back to the AUTOMATIC ope...

Page 137: ...rd Page 137 165 Appendix A Dimensions 136 0 mm 1 50 99 93 83 48 105 111 X5 X1 130 8 0 mm 111 0 mm 136 0 mm 54 24 60 25 144 0 mm 32 0 mm 42 0 mm 144 0 mm 12 0 mm 2002 11 21 MFR 3 Dimensions r3ww 4702 a...

Page 138: ...Gen 3 0 Irated IMains 1 5 Irated Power consumption 0 15 W Rated short to time current 1 s 5 10 0 Irated Ambient variables Power supply 12 24 Vdc 9 5 to 32 Vdc Intrinsic consumption max 15W Ambient tem...

Page 139: ...Resolution PWM 8 12 Bit depending on model 0 4 to 20 mA output Maximum load 500 0 to 10 V 5 V output Internal resistance 1 k Interface isolated Insulation voltage 3 000 Vdc Version variable Housing T...

Page 140: ...MW 2 Re to active power Actual value in L1 L2 L3 32 0 to 32 0 Mvar 2 Power factor cos Actual power factorL1gen mains value i0 00 to 1 00 to c0 00 Miscellaneous Real energy 0 to 4 200 GWh not calibrat...

Page 141: ...or 1 e g 0030 corresponds to i0 70 3 Generator frequency Hz 100 0 lower frequency e g 0000 corresponds to 00 00 Hz 100 upper frequency e g 7000 corresponds to 70 00 Hz 4 Generator re active power kvar...

Page 142: ...y scaleable 15 Analog input T5 C or F or freely scaleable 16 Analog input T6 C or F or freely scaleable 17 Analog input T7 C or F or freely scaleable 18 additional freely scaleable analog in put termi...

Page 143: ...wer of 3 000 kW is exceeded Igen prim Vgen prim 3 3 000 kW The description 0 corresponds to the minimum input of 4 mA or 0 mA the description 100 corresponds to the maximum input of 20 mA The values c...

Page 144: ...e limit exceeded Synchronization GCB 30 Generator re active power capacitive 33 Generator re active power inductive 32 Ground failure 33 Battery undervoltage 34 Interface failure terminals X1 to X5 35...

Page 145: ...is happening 88 Lamp test activated 89 Malfunction Reply GCB is open failure during closing 90 Malfunction Reply MCB is open failure during closing 91 Malfunction Reply GCB is open failure during ope...

Page 146: ...Bit 14 1 Internal Bit 13 1 Internal Bit 12 1 Internal Bit 11 1 Internal Bit 10 1 Internal Bit 9 1 Internal Bit 8 1 Internal If both bits are set for double bits the input is activated Bit 7 1 Bit 6 1...

Page 147: ...Bit 0 1 Internal 4 2 14 Internal alarms 6 Bit 15 1 Internal Bit 14 1 Internal Bit 13 1 Dead bus start error time overrun FS Control input not active F0 Class F0 alarm not active F1 Class F1 alarm acti...

Page 148: ...3 33 H B busbar status L B internal FFH Voltage and frequency present 00H Voltage and frequency not present 11 1 34 Mains voltage delta V23 V 10VmainsEXPO 11 2 35 Mains voltage delta V31 V 10VmainsEX...

Page 149: ...overfrequency Bit 13 1 Bit 12 1 F0 Mains underfrequency If both bits are set for double bits the input is activated FS Control input not active F0 Class F0 alarm not active F1 Class F1 alarm active un...

Page 150: ...minal 68 Discrete input D07 Bit 9 1 Bit 8 1 Terminal 69 Discrete input D08 Bit 7 1 Bit 6 1 Terminal 70 Discrete input D09 Bit 5 1 Bit 4 1 Terminal 71 Discrete input D10 Bit 3 1 Bit 2 1 Terminal 72 Dis...

Page 151: ...for start stop synchronizing the MFR The following three data words can be re ceived by the MFR Refer to the GW 4 manual on how to control several MFR units MUX No Contents words Unit Note 1 1 1 Set p...

Page 152: ...word 3 high byte In a visualization message the byte 0 is always used to show the hexadecimal value DD This one defines the message as a visualization message Since the complete transmission telegram...

Page 153: ...e value transmitted is then 01 00 0000 1001 0110 B 4096 H E power of 300 kW is to be compensated The value transmitted is then 00 00 0001 0010 1100 B 012C H I power of 600 kW is to be compensated Nega...

Page 154: ...01 Generator freq f set 40 0 to 70 0 Hz 50 0 Hz Rated system frequency 50 60 Hz 50 0 Hz Gen volt transf secondary 50 to 125 V 50 to 480 V 100 V Gen volt transf primary 0 005 to 65 000 0 020 to 65 000...

Page 155: ...ntroller reset Tn 0 0 to 60 0 s 1 00 s Volt controller derivat Tv 0 00 to 6 00 s 0 00 s Pow fact contr ON OFF OFF on off on off Pow fact contr setpoint i0 70 to 1 00 to c0 70 1 00 Power factor externa...

Page 156: ...B dead bus op ON OFF ON on off on off GCB dead bus op df max 0 05 to 5 00 Hz 0 45 Hz GCB dead bus op dV max 0 1 to 20 10 0 GCB dead bus op max time 0 to 999 s 030 s MCB dead bus op ON OFF ON on off on...

Page 157: ...0 Hz 58 00 Hz Gen overfreq 2 Delay 0 02 to 99 98 s 00 10 s Gen underfreq monitoring ON OFF OFF on off on off Gen underfreq 1 f 40 00 to 85 00 Hz 45 00 Hz Gen underfreq 1 Delay 0 02 to 99 98 s 01 00 s...

Page 158: ...ayed by 9ABC eng speed Y N NNNN Dig input 9ABC error class 0 to 3 1111 Errortxt term 62Terminal 62 any Terminal 62 Errortxt term 63Terminal 63 any Terminal 63 Op mod blocked by Ter 63 ON OFF OFF Error...

Page 159: ...Pulse kWh 0 1 to 150 0 001 0 Pulse output 2 kvarh kvarh Pulse output 2 logic positive negative negative Reactive energy Pulse kvah 0 1 to 150 0 001 0 CONFIGURE DRIVE Configure Drive YES NO YES Y N Y...

Page 160: ...ses your problem can be resolved over the phone If not you can select which course of action you wish to pursue based on the available services listed in this section Returning Equipment For Repair If...

Page 161: ...epartment in Stuttgart 49 0 711 789 54 0 They will help expedite the processing of your order through our distributors or local service facility To expedite the repair process contact Woodward in adva...

Page 162: ...the following international Woodward facilities to obtain the address and phone number of the facility nearest your location where you will be able to get information and service Facility Phone number...

Page 163: ...r toll free or local phone numbers e mail us or use our website and refer ence technical support Product Training is available on site from several of our worldwide facilities at your location or from...

Page 164: ..._________ REV ____________ Unit type MFR 3 ____________________________________ Serial number S N _______________________________________ Description of your problem __________________________________...

Page 165: ...9 70565 Stuttgart Germany Phone 49 0 711 789 54 0 Fax 49 0 711 789 54 100 stgt info woodward com Homepage http www woodward com power Woodward has company owned plants subsidiaries and branches as wel...

Reviews: