Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 155/165
Option
Parameter
100/400V; 5 A
Setting range
Standard
setting
Customer settings
Lev
el
CONFIGURE CONTROLLER
Configure Controller
YES/NO NO
Y N
Y N
Power controller
Pset1
C/E/I 0 to 16,000 kW
C000200kW
Power controller
Pset2
C/E/I 0 to 16,000 kW
C000100kW
Initial state
Frequency
0 to 100 %
50 %
Freq.controller
ON/OFF ON
on off
on off
f-contr. active
at:
0.0 to 70.0 Hz
30,0 Hz
Delay time for f to contr.
0 to 999 s
005 s
Freq.controller ramp
1 to 50 Hz/s
05 Hz/s
F/P contr.type
THREEST. / ANALOG / PWM
ANALOG
Freq.controller dead
band
0.02 to 1.00 Hz
0.10 Hz
Freq.controller time pulse>
10 to 250 ms
080 ms
Freq.controller gains.Kp
0.1 to 99.9
10.0
F/P contr.output
see table
+/-10V
Level PWM
3.0 to 10.0 V
3.0V
Freq.controller gain.Kpr
1 to 240
20
Freq.controller reset
Tn
0.0 to 60.0 s
1.00 s
Freq.controller derivat.Tv
0.00 to 6.00 s
0.00 s
Starting point
voltage
0 to 100 %
50%
Volt.controller
ON/OFF ON
on off
on off
V/Q contr.type
THREESTEP / ANALOG
ANALOG
Volt.controller dead
band
0.1 to 15.0 V / 0.5 to 60.0 V
00.5%
Volt.controller time pulse>
20 to 250 ms
080 ms
Volt.controller gain.Kp
0.1 to 99.9
10.0
V/Q contr.output
see table
+/-10V
Volt.controller gain.Kpr
1 to 240
20
Volt.controller reset
Tn
0.0 to 60.0 s
1.00 s
Volt.controller derivat.Tv
0.00 to 6.00 s
0.00 s
Pow.fact.contr.
ON/OFF OFF
on off
on off
Pow.fact.contr. setpoint
i0.70 to 1.00 to c0.70
1.00
Power factor
external
ON/OFF OFF
on off
on off
Analog input
0 to 20 / 4 to 20 mA
4 to 20 mA
Ext. Pow.Factor
0mA
i0.70 to 1.00 to c0.70
Ext. Pow.Factor
20mA
i0.70 to 1.00 to c0.70
Pow.fact.contr. dead
band
0.5 to 25.0 %
01.0 %
Pow.fact.contr. gain
Kp
0.1 to 99.9
10.0
Pow.fact.contr. gains
Kpr
1 to 240
20
Pow.fact.contr. reset
Tn
0.0 to 60.0 s
1.00 s
Pow.fact.contr. derivat.Tv
0.00 to 6.00 s
0.00
Power controller
ON/OFF ON
on off
on off
Power controller
ramp
0 to 100 %/s
005 %/s
Power controller
ramp
1 to 100 kW/s
20 %/s
Power limit
P max.
10 to 120 %
100 %
Power limit
P min.
0 to 50 %
00 %
Power setpoint
external
ON/OFF ON
on off
on off
Analog input
0 to 20 / 4 to 20 mA
4 to 20 mA
Ext.setpoint 0mA
C/E/I 0 to 16,000 kW
C00000kW
Ext.setpoint 20mA
C/E/I 0 to 16,000 kW
C00200kW
Power controller dead band
0.1 to 25.0 %
01.0 %
Power controller
gain Kp
0.1 to 99.9
20.0
Powercontr. dead band ratio
1.0 to 9.9
*2.0
Power controller
gain Kpr
1 to 240
20
Power controller
reset Tn
0.0 to 60.0 s
1.00 s
Power controller derivat.Tv
0.00 to 6.00 s
0.00
Warm up load
limit value
5 to 110 %
015 %
Warm up load
time
0 to 600 s
000 s
Active power
load share
ON/OFF ON
on off
on off
Act.load share
factor
10 to 99 %
50 %
Reactive power
load share
ON/OFF OFF
on off
on off
React.load share
factor
10 to 99 %
50 %